![Fuji Electric Time Delta-C FSV-2 Скачать руководство пользователя страница 63](http://html1.mh-extra.com/html/fuji-electric/time-delta-c-fsv-2/time-delta-c-fsv-2_instruction-manual_2341899063.webp)
-56-
4.12.2.6. Totalization processing at error (Burnout)
Description
BURNOUT (TOTAL)
Determines how to react such errors that the measurement status is abnormal on account of an empty pipe interior or bubbles mixed
in fluid (common to total indication and total pulse output).
Settable range:
HOLD
: Stops the total (as factory set).
NOT USED : Continues the total according to the measured value marked immediately before the error occurrence.
BURNOUT TIMER
Sets the time from error occurrence to error processing.
Settable range: 10 to 900sec (factory set: 10sec) Please set 10 seconds or more.
The total continues until the burnout timer is activated.
In energy measurement mode, totalization also stops at a hardware error such as a break in a resistance bulb (RTD).
For actual keying, refer to the typical operation indicated below. Set the protection to OFF beforehand. (See Section 4.5.1.)
Operation
(example)
Change the processing from "BURNOUT" to "HOLD", and change the burnout timer setting from 10 seconds to 15
seconds.
*Below is an example for 1-path/energy measurement and 2-path measurement. Refer to Section 4.8.1 for channel
designation of 2-pipe measurement.
Key operation
Description
Display
▼
Press the
key twice to display “OUTPUT SETUP”.
OUTPUT SETUP
ENT
▼
Press the
ENT
key once to display “ZERO ADJUSTMENT”.
ZERO ADJUSTMENT
SET ZERO
▼
Press the
key for 5 times to display “TOTAL”.
TOTAL
ENT
▼
Press the
ENT
key once to display “TOTAL MODE”.
TOTAL MODE
START
Press the
key for 4 times to display “BURNOUT(TOTAL)”.
Because HOLD (factory set) is already registered, go to the next step.
BURNOUT(TOTAL)
HOLD
▼
▼
▼
▼
Note) For setting “NOT USED”, press the //ENT key, and the /// key to
select “NOT USED”.
▼
Press the
key once to display “BURNOUT TIMER”.
BURNOUT TIMER
10sec
ENT
▼
Press the
ENT
key once to blink the cursor.
BURNOUT TIMER
0
10sec
▼
Press the
key twice to move the cursor.
BURNOUT TIMER
01
0
sec
▼
Press the
key for 5 times to set “5”.
BURNOUT TIMER
01
5
sec
Press the
ENT
key once to register.
BURNOUT TIMER
COMPLETE
↓
ENT
▼
▼
▼
▼
―――
BURNOUT TIMER has been registered.
―――
BURNOUT TIMER
15sec
ESC
Press the
ESC
key twice and then press the
key for 3 times to enter
the measurement mode.
0.00 m3/h
+ 0.00 m3