4.13.5.3. Flow switch
Description
Select a contact output as DO1, DO2, DO3, and/or DO4 when the flow rate exceeds a setting.
Select a contact output as DO1, DO2, DO3, and/or DO4 when the instantaneous energy exceeds a setting. (for 1-path/energy
measurement)
Flow rate
FLOW SW HIGH SWITCH
Time
Hysteresis
ON or OFF
Flow rate
FLOW SW LOW SWITCH
Time
ON or OFF
Hysteresis
Settable range
Flow rate
: 0 to 32m/s in terms of flow velocity.
Thermal flow : 0.000001 to 99999999
Action
: FLOW SW HIGH or FLOW SW LOW
FLOW SW HIGH(Thermal) or FLOW SW LOW(Thermal )
Contact action : ACTIVE ON : DO1/DO2/DO3/DO4: Normally off
ACTIVE OFF : DO1/DO2/DO3/DO4: Normally on
Note) The hysteresis value set in Section 4.12.1 "Setting of flow rate range” is applied to the action range.
For actual keying, refer to the typical operation indicated below. Set the protection to OFF beforehand. (See Section 4.5.1.)
Operation
(example)
Set the DO1 output to “FLOW SW HIGH”, and upper limit flow rate to 12 [m
3
/h].
Also, set the contact to “ACTIVE ON”.
* Below is an example for 1-path/energy measurement. Refer to Section 4.8.1 for channel designation of 2-path
measurement and 2-pipe measurement.
Key operation
Description
Display
▼
Press the
key twice to display “OUTPUT SETUP”.
OUTPUT SETUP
ENT
▼
Press the
ENT
key once to display “ZERO ADJUSTMENT”.
ZERO ADJUSTMENT
SET ZERO
▼
Press the
key for 8 times to display “DO1 OUT”.
* Use the
key to select “DO2 OUT”, “DO3 OUT”, or “DO4 OUT”.
DO1 OUT
NOT USED
ENT
▼
Press the
ENT
key once to blink the cursor.
DO1 OUT
NOT USED
▼
Press the
key for 5 times to display “FLOW SWITCH” on the 2nd
line.
DO1 OUT
FLOW SWITCH
ENT
▼
Press the
ENT
key once to display the flow rate setting screen of “FLOW
SW HIGH”.
* Press the
key once to display the flow rate setting screen of
“FLOW SW LOW”.
FLOW SW HIGH
10.0000 m3/h
ENT
▼
Press the
ENT
key once to blink the cursor.
FLOW SW HIGH
0
010.0000 m3/h
▼
Press the
key for 3 times to move the cursor.
FLOW SW HIGH
001
0
.0000 m3/h
▼
Press the
key twice to set “2”.
FLOW SW HIGH
001
2
.0000 m3/h
ENT
▼
Press the
ENT
key once to register.
FLOW SW HIGH
COMPLETE
↓
▼
▼
―――
“FLOW SW HIGH” has been registered.
―――
STATUS OUT
CONTACT ACTION