4.12.3.1. Total pulse output
Description
Sets the total pulse output for DO1 OUT, DO2 OUT, DO3 OUT, and/or DO4 OUT.
+ TOTAL PULSE: Outputs flow rate total pulse in forward direction.
- TOTAL PULSE : Reverse flow rate total pulse output.
H: TOTAL PULSE(T): Total pulse output of totalized heating energy.
C: TOTAL PULSE(T): Total pulse output of totalized cooling energy.
Note) Refer to Section 4.12.2.1.to set the flow total rate, pulse width, etc.
Note) Refer to Section 4.12.2.3 to set the energy total rate, pulse width, etc.
For actual keying, refer to the typical operation indicated below. Set the protection to OFF beforehand. (See Section 4.5.1.)
Operation
(example)
Set the DO1 output to “+ TOTAL PULSE”.
Also, set the contact to “ACTIVE ON”.
* Below is an example for 1-path/energy measurement. Refer to Section 4.8.1 for channel designation of 2-path
measurement and 2-pipe measurement.
Key operation
Description
Display
▼
Press the
key twice to display “OUTPUT SETUP”.
OUTPUT SETUP
ENT
▼
Press the
ENT
key once to display “ZERO ADJUSTMENT”.
ZERO ADJUSTMENT
SET ZERO
▼
Press the
key for 6 times to display “DO1 OUT”.
* Press the
key again to display “DO2 OUT”.
* Press the
key again to display “DO3 OUT”.
* Press the
key again to display “DO4 OUT”.
DO1 OUT
NOT USED
ENT
▼
Press the
ENT
key once to blink the cursor.
DO1 OUT
NOT USED
▼
Press the
key once to display “+ TOTAL PULSE ” on the 2nd line.
* Use the
key to select “- TOTAL PULSE”, “H: TOTAL PULSE(T)”, or
“C: TOTAL PULSE(T)”.
DO1 OUT
+TOTAL PULSE
Press the
ENT
key once to register “+TOTAL PULSE”.
DO1 OUT
COMPLETE
↓
ENT
▼
▼
▼
▼
―――
“+TOTAL PULSE” has been registered.
―――
STATUS OUT
CONTACT ACTION
ENT
▼
Press the
ENT
key once to display “CONTACT ACTION”.
CONTACT ACTION
ACTIVE ON
Press the
ENT
key once to register “ACTIVE ON” (normally off).
* To select normally on, press the
key.
CONTACT ACTION
COMPLETE
↓
ENT
▼
▼
▼
▼
―――
“ACTIVE ON” has been registered.
―――
STATUS OUT
CONTACT ACTION
ESC
Press the
ESC
key twice and then press the
key for 3 times to enter
the measurement mode.
0.000 m3/h
0.000 m3