-11-
3.3.4. How to connect to terminal block
3.3.4.1. Cable treatment
Although the cables can be connected to the terminals with bare wire, we recommend using bar terminal (ferrule) for
connecting cables.
When you cut and use the signal cable, make sure to cut the cable in same length of upstream and downstream.
Note) if cable lengths are different, it may adversely affect the output.
Usable wiring materials
16
10
øD1
øD2
Approx. 10mm
AWG20
to
AWG16
• Wire
Gauge: AWG20 (0.5mm
2
) to AWG16 (1.5mm
2
)
Strip-off length: approx. 10mm
• Bar terminal
Wire end ferrule (with insulation cover)
Weidmuller
www.weidmuller.com
Wire size (mm
2
)
AWG
øD1 (mm)
øD2 (mm)
Type
0.5 20 1 2.6 H0.5/16
0.75 18 1.2 2.8 H0.75/16
1 17 1.4
3 H1/16
1.5 16 1.7 3.5 H1.5/16
Note1) Make sure to use PZ6/5(H0.25 to H6 for sleeve) as a crimp tool for caulking.
Note2) Applicable sleeve is required for electric wire.
Note3) Insert the electric wire to the end of ferrule so as to crimp.
Note4) Length of stripped wire is 12mm.