FVR-C11S-EN
6
Safety Instructions
Instructions on wiring
WARNING
1. When the inverter is connected to power,
connect it via a line-protection molded case
circuit breaker or an earth-leakage circuit
breaker (Residual current operated protec-
tive device).
Otherwise fire could occur.
2. Be sure to connect the ground wire.
Otherwise electric shock or fire could
occur.
3. Ensure that a licensed specialist
performs the wiring work.
4. Check before starting the wiring that the
power is off (OPEN).
Otherwise electric shock could occur.
5. Do not wire up the inverter until it has been
installed securely.
Otherwise electric shock or injury could
occur.
6. The inverter has to be grounded in accord-
ance with the national and local safety
specification.
Otherwise electric shock could occur.
CAUTION
1. Check that the number of phases and the
rated voltage of this product correspond to
the number of phases and voltage of the
AC power supply.
Otherwise fire could occur.
2. Do not connect the AC power supply to the
output terminals (U, V, W).
Otherwise injury could occur.
3. Check the output terminals (U,V,W) for the
phase order and connect them to the motor
correctly.
Otherwise fire could occur.
4. Do not connect a braking resistor directly to
the DC terminals [P(+), N(-)].
Otherwise fire could occur.
5. Noise is generated from the inverter, mo-
tor, and wiring. Take care that this noise
does not cause malfunctions in peripheral
sensors and equipment.
Otherwise accidents could occur.