5-6
5 Selecting Function
FVR-C11S-EN
5
Change during operation: X = impossible,
= possible (enabled by using
),
= possible (enabled by using
)
Table 5-1-1
Table of Function Selection List
Note:
For details on "o01" to "o11", refer to the instruction manual that came with the optional
RS485 serial communication unit.
Func-
tion
code
No.
Name
Setting range
Unit
Min.
unit
Factory
setting
Change
during
opera-
tion
User
set-
ting
o02
Selection of
operation in error
occurrence
0: Er8 trip with eight continuous commu-
nication errors or check sum errors
1: Er8 trip after the time (o03) set in the
timer elapses with eight continuous
communication errors or check sum
errors
2: Er8 trip if communication does not re-
cover until the time (o03) set in the tim-
er elapses
3: Retry and operation continuation with
communication or check sum error
-
-
0
o03
Selection of time
set in timer
1 to 60s
s
1
2
o04
Transmission
rate
0: 19200bps
1: 9600bps
2: 4800bps
3: 2400bps
4: 1200bps
-
-
1
o05
Data length
selection
0:8bits
1:7bits
-
-
0
o06
Parity bit
selection
0: No parity
1: Even parity
2: Odd parity
-
-
0
o07
Stop bit selection 0:2bits
1:1bit
-
-
0
o08
Communication
discontinuation
detection time
0: No detection,1 to 60s
s
1
0
o09
Response
interval
0.00 to 1.00
s
0.01
0.01
v
o10
RS485
command selec-
tion (frequency
setting)
0: Selection of frequency setting
selected with F01
1: Selection of frequency setting
from RS485
-
-
0
X
o11
RS485
command selec-
tion (operation
command)
0: Selection of operation command
selected with F02
1: Selection of operation command from
RS485
-
-
0
X