2
Safety Instructions
FVR-C11S-EN
Compliance with UL/cUL standards [Applicable to products with UL/cUL mark]
1. [WARNING] Take care of electric shock. Be sure to turn the
inverter off before starting work.
2. [CAUTION] When the charge lamp is lit, the inverter is still charged
at a dangerous voltage.
3. [WARNING] There are two or more live parts inside the inverter.
4. The inverter is approved as a part used inside a panel. Install it in-
side a panel.
5. Perform wiring to the input, output and control terminals of the in-
verter, referring to the table below. Use UL certified round crimp
terminal to the input and output terminals with insulation cover or
covered with reduced tube to obtain the insulation distance. Use a
crimping tool recommended by the terminal manufacturer when
fabricating crimp terminals.
6. Install a fuse in the power supply to the inverter, referring to the ta-
ble below.
Voltage
Inverter type
Tightening torque
[Nm]
Applicable wire diameter
[AWG] (mm
2
)
1)
Fuse
[A]
2)
Recommended fuse
L1/L, L2/N
U, V, W
Control
section
L1/L, L2/N
U, V, W
Control
section
Gould
Company
Bussmann
Company
Single-
phase
200V
input
FVR0. 1C11S-7EN
1.2
0.4
14 (2.1)
20 (0.5)
6
A4J6
JKS6
FVR0. 2C11S-7EN
6
A4J6
JKS6
FVR0. 4C11S-7EN
10
A4J10
JKS10
FVR0. 75C11S-7EN
15
A4J15
JKS15
FVR1. 5C11S-7EN
12 (3.3)
30
A4J30
JKS30
FVR2. 2C11S-7EN
1.8
10 (5.3)
40
A4J40
JKS40
1) Use copper wires of allowable maximum temperature 60 or75 °C.
2) Use UL certified "quick breaking fuse".
7. Connect the power supply satisfying the characteristics shown in
the table below as an input power supply of the inverter. (Short
circuit rating)
Inverter type
Input max. voltage
Input current
FVR0. 1-2. 2C11S-7EN
AC240V
5,000 A or less
CAUTION