5-2
5 Selecting Function
FVR-C11S-EN
5
Change during operation: X = impossible,
= possible (enabled by using
),
= possible (enabled by using
)
Function
code No.
Name
Setting range
Unit
Min.
unit
Factory
setting
Change
during
opera-
tion
User
setting
F10
Electronic
thermal overload
relay for motor
(Select)
0: Inactive
1: Active (for 4-pole standard motor)
2: Active (for 4-pole FUJI inverter motor)
-
-
1
F11
(Level)
20 to 135% of inverter rated current
A
0.01
Typical
value of
FUJI
4-pole
motor
F12
(Thermal
time
constant)
0.5 to 10.0min
min
0.1
5.0
F14
Restart after mo-
mentary power
failure (Select)
0: Inactive (Trip and alarm when power fail-
ure occurs)
1: Inactive (Trip and alarm when power re-
covers)
2: Active (Momentarily stops and restarts at
setting frequency of before power failure)
3: Active (Momentarily stops and restarts at
starting frequency)
-
-
0
X
F15
Frequency
limiter
(High)
0 to 120Hz
Hz
1
70
F16
(Low)
0 to 120Hz
0
F17
Gain
(for frequency
setting signal)
0: For 0 to 10VDC (4 to 20 mA DC)
1: For 0 to 5VDC (4 to 12 mA DC)
-
-
0
X
F18
Bias frequency
-120 to 120Hz
Hz
1
0
F20
DC injection brake
(Starting
freq.)
Fixed to 3Hz
Hz
-
3.0
-
F21
(Level)
0 to 100%
%
1
50
F22
(Braking
time)
0.0 s (Inactive), 0.1 to 30.0 s
s
0.1
0.0
F23
Starting
frequency
1 to 6Hz
Hz
1
1
X
F24
-
Data cannot be changed.
-
-
0.0
-
F25
Stop frequency
1 to 6Hz
Hz
1
1
X