FVR-C11S-EN
2-6
2 Installation and Connection
2
2-3-3 Connecting the control terminals
Table 2-3-4 lists the functions of the control cir-
cuit terminals.
The method of connecting a control circuit termi-
nal depends on how its function is set.
Connect the control circuit terminals according
to the set functions.
1) Digital input terminal
Figure 2-3-3 shows the circuit configuration.
Use a reliable contact without poor contact for
input.
Example: FUJI control relay HH54PW
a) When SW7 is set to CM (factory setting)
b) When SW7 is set at P24
Figure 2-3-3 Digital input terminal
2) Run/stop command terminal [FWD, REV]
These terminals are left open in the factory.
Pressing the
key on the keypad panel
starts forward operation. When function F02
is set at 0 or 1, the terminal functions are as
shown in Table 2-3-3.
SW7
P24
F1
0 V
P24/CM
CM
4.7k
FVR-C11S-7EN
+24 to
+27VDC
+24 to
+27VDC
FWD or others
SW7
P24
F1
0 V
40mA max.
P24/CM
CM
4.7k
FVR-C11S-7EN
FWD or others
+24 to
+27VDC