![Fuji Electric FVR-C11S-7EN Series Скачать руководство пользователя страница 43](http://html1.mh-extra.com/html/fuji-electric/fvr-c11s-7en-series/fvr-c11s-7en-series_instruction-manual_2341873043.webp)
5 Selecting Function
5-3
FVR-C11S-EN
5
Change during operation: X = impossible,
= possible (enabled by using
),
= possible (enabled by using
)
Func-
tion
code
No.
Name
Setting range
Unit
Min.
unit
Factory
setting
Change
during
opera-
tion
User
set-
ting
F26
Motor sound
(carrier freq.)
0 to 15kHz
0.75kHz is set when 0 is specified
kHz
1
15
F27
(sound tone )
0: Level 0
1: Level 1
2: Level 2
3: Level 3
-
-
0
F30
FM terminal
(Voltage
adjust)
0 to 200%
%
1
100
F31
(Function)
0: Output frequency
1: Output current
2: PID feedback amount
3: DC link circuit voltage
-
-
0
F36
30Ry operation
mode
0: Excited when tripped
1: Normally excited
-
-
0
X
E: Extension Terminal Functions
Func-
tion
code
No.
Name
Setting range
Unit
Min.
unit
Factory
setting
Change
during
opera-
tion
User
set-
ting
E01
X1 terminal
(function
selection)
X2 terminal
(function
selection)
X3 terminal
(function
selection)
Use the code values listed below to select
[X1], [X2] and [X3] terminal functions.
-
-
0
X
E02
-
-
2
X
E03
-
-
3
X
0: Multistep frequency 1 (SS1)
1: Multistep frequency 2 (SS2)
2: Coast-to-stop command (BX)
3: Alarm reset (RST)
4: External alarm (THR)
5: Write enable command for keypad
(WE-KP)
6: PID control cancel (Hz/PID)
7: Link operation selection (LE)