"Maximum permitted feed-in power of the entire system"
Input field for the "Maximum permitted feed-in power of the entire system" in W or %
(setting range: -10 to 100%).
If there is no meter in the system or if a meter has failed, the inverter limits the feed-in
power to the set value.
Example: Feed-in limitation
(without consideration of the efficiency)
PV system on Fronius inverter:
5000 W
Consumption in home:
1000 W
Maximum permitted feed-in power of the entire system:
60% = 3000 W
Case 1: The battery can be charged
Power at grid feed-in point:
0 W
Power at inverter output:
1000 W
Power into the battery:
3000 W
Case 2: The battery cannot be charged
Power at grid feed-in point
3000 W
Power at inverter output:
4000 W
Power into the battery:
0 W
In this example, no more than 3000 W may be fed into the grid at the grid feed-in
point. However, any loads that are located between the inverter and the grid feed-in
point can be supplied by additional power from the inverter. These loads are also com-
pensated as required.
Dynamic power
regulation with
several inverters
Example 1: Fronius SnapINverter ≤ Fronius Symo GEN24
Only 1 primary meter is required for the Fronius Symo GEN24 inverter.
The power values shown are an example. Inverter configurations with power values oth-
er than those shown in the example are possible, taking into account the criteria for this
example.
IMPORTANT!
Zero feed-in is not possible when using 2 inverters.
91
EN
Содержание Symo GEN24 3.0
Страница 2: ......
Страница 11: ...General information 11...
Страница 12: ...12...
Страница 31: ...Backup power variant PV Point OP 31...
Страница 32: ...32...
Страница 34: ...34...
Страница 35: ...Installation 35...
Страница 36: ...36...
Страница 77: ...Settings website of the inverter 77...
Страница 78: ...78...
Страница 104: ...104...
Страница 105: ...Options 105...
Страница 106: ...106...
Страница 115: ...2 Set the DC disconnector to the On switch position Switch on the automatic circuit breaker 115 EN...
Страница 116: ...116...
Страница 117: ...Appendix 117...
Страница 118: ...118...
Страница 132: ...132...
Страница 133: ...Circuit diagrams 133...
Страница 134: ...134...
Страница 135: ...Circuit Diagram PV Point OP Circuit Diagram 135 EN...
Страница 136: ...Fronius Symo GEN24 and BYD Battery Box Premi um HV Circuit Diagram 136...
Страница 137: ...Wiring diagram surge protective device SPD Circuit Diagram 137 EN...
Страница 138: ...138...
Страница 139: ...Dimensions of the inverter 139...
Страница 140: ...140...
Страница 141: ...Fronius Symo GEN24 3 5 kW Fronius Symo GEN24 3 5 kW 141 EN...
Страница 142: ...142...
Страница 143: ...143 EN...
Страница 144: ......