Copper: round, solid
-
Copper: round, fine-stranded
IMPORTANT!
Connect the individual conductors to an appropriate ferrule if several individual conduct-
ors are connected to one input of the push-in terminals.
WSD connections with push-in terminal
Dis-
tance
max.
Stripping
length
Solid
Fine-stran-
ded
Fine-stran-
ded with fer-
rules with
collar
Fine-stran-
ded with fer-
rules without
collar
Cable recom-
mendation
100 m
109 yd
10 mm
0.39 inch
0.14-1.5 mm
2
AWG 26-16
0.14-1.5 mm
2
AWG 26-16
0.14-1 mm
2
AWG 26-18
0.14-1.5 mm
2
AWG 26-16
min. CAT 5
UTP (unshiel-
ded twisted
pair)
Modbus connections with push-in terminal
Dis-
tance
max.
Stripping
length
Solid
Fine-stran-
ded
Fine-stran-
ded with fer-
rules with
collar
Fine-stran-
ded with fer-
rules without
collar
Cable recom-
mendation
300 m
328 yd
10 mm
0.39 inch
0.14-1.5 mm
2
AWG 26-16
0.14-1.5 mm
2
AWG 26-16
0.14-1 mm
2
AWG 26-18
0.14-1.5 mm
2
AWG 26-16
min. CAT 5
STP (shielded
twisted pair)
IO connections with push-in terminal
Dis-
tance
max.
Stripping
length
Solid
Fine-stran-
ded
Fine-stran-
ded with fer-
rules with
collar
Fine-stran-
ded with fer-
rules without
collar
Cable recom-
mendation
30 m
32 yd
10 mm
0.39 inch
0.14-1.5 mm
2
AWG 26-16
0.14-1.5 mm
2
AWG 26-16
0.14-1 mm
2
AWG 26-18
0.14-1.5 mm
2
AWG 26-16
Single con-
ductor pos-
sible
LAN connections
Fronius recommends using at least CAT 5 STP (shielded twisted pair) cables and a maximum distance of
100 m (109 yd).
Cross section of
the AC cable
For a standard M32 metric screw joint with a reducer:
Cable diameter from 7-15 mm
When using an M32 metric screw joint (reducer removed):
cable diameter from 11-21 mm
(with a cable diameter of less than 11 mm, the strain-relief force is reduced from 100 N to
a maximum of 80 N)
With cable diameters greater than 21 mm, the M32 screw joint must be replaced by an
M32 screw joint with a larger clamping area – item number: 42,0407,0780 – strain-relief
device M32 x 1.5 KB 18–25.
46
Содержание Symo GEN24 3.0
Страница 2: ......
Страница 11: ...General information 11...
Страница 12: ...12...
Страница 31: ...Backup power variant PV Point OP 31...
Страница 32: ...32...
Страница 34: ...34...
Страница 35: ...Installation 35...
Страница 36: ...36...
Страница 77: ...Settings website of the inverter 77...
Страница 78: ...78...
Страница 104: ...104...
Страница 105: ...Options 105...
Страница 106: ...106...
Страница 115: ...2 Set the DC disconnector to the On switch position Switch on the automatic circuit breaker 115 EN...
Страница 116: ...116...
Страница 117: ...Appendix 117...
Страница 118: ...118...
Страница 132: ...132...
Страница 133: ...Circuit diagrams 133...
Страница 134: ...134...
Страница 135: ...Circuit Diagram PV Point OP Circuit Diagram 135 EN...
Страница 136: ...Fronius Symo GEN24 and BYD Battery Box Premi um HV Circuit Diagram 136...
Страница 137: ...Wiring diagram surge protective device SPD Circuit Diagram 137 EN...
Страница 138: ...138...
Страница 139: ...Dimensions of the inverter 139...
Страница 140: ...140...
Страница 141: ...Fronius Symo GEN24 3 5 kW Fronius Symo GEN24 3 5 kW 141 EN...
Страница 142: ...142...
Страница 143: ...143 EN...
Страница 144: ......