28

Error Code

Error

Solution

A

Containment Tightness

Refer to the Containment Tightness Testing section of this guide and 

perform the tests in that section to ensure that there are no leaks and that 

the tank is tight.

B

Thermal Contraction

Caused by temperature variations of the air (or liquid if present) in the 

containment.

C

Liquid in Containment

This will decrease the containment size. If liquid is drawn through 

the containment, through the STP siphon, various parameters and 

containment vacuum readings will be incorrect. Containments should 

remain free of liquid at all times.

D

Siphon Function Check

The siphon must be able to pull a vacuum of 8" Hg or more if connected 

to other equipment. The vacuum also must have a minimum flow rate of 

146 L/Hr. Perform a STP Siphon Flow Rate Test as illustrated in the Pre-

Operational Containment Testing chapter.

E

SCM Vacuum Sensor 

Function Check

The transducer is sending incorrect data or no data to the console. Verify 

wiring from the transducer to the console. If wiring is correct, setup and 

program the transducer on a different, unused channel for testing.

F

STP Function Check

Use the dispenser to signal the STP when the dispenser is authorized 

then the STP should run. Also, TS-SCM must be able to signal the STP 

pump on. Force a test on the containment using the TS-SCM Control 

screen. The STP will start only if necessary to evacuate the containment. 

If the STP does not run to evacuate the containment, verify programming.

G

Verify Programming

Refer to the TS-SCM Setup chapter of this guide for all TS-SCM related 

programming information.

H

SCM Vacuum Relief 

Valve Function Check

The mechanical vacuum relief valve is designed to open when 

containment vacuum levels reach or exceed 10" Hg. If at any time the 

containment vacuum level exceeds 10" Hg while the pump is on, this error 

will occur as an indication of a relief valve failure. 

CLEARING ALARMS

Clearing a console of alarms is important because, depending on how the console has been set up, 

alarms can: disable channels, start an annunciator, or stop an TS-SCM test under way.
Administrator privileges will be necessary to clear TS-SCM alarms on the console. For instructions on 

how to obtain an Administrator access level, see the list of programming manuals in the “ADDITIONAL 

DOCUMENTATION” section.

1.  Identify the alarm on the TS-SCM Alarms screen.
2.  Diagnose the condition using information found in the Alarms chapter of this guide.
3.  Follow the troubleshooting steps in the previous section of this chapter to correct the issues 

indicated by the alarms.

4.  Navigate to the TS-SCM Control screen.
5.  Select Reset Alarms on the Control screen. 

NOTE

: If the condition still exists, the alarm can take up to several hours to reappear after the 

containment is enabled.

Содержание TS-SCM

Страница 1: ...TS SCM SECONDARY CONTAINMENT MONITORING INSTALLATION GUIDE...

Страница 2: ...evere injury or death if you do not follow standard industry practices and the instructions in this manual Before you work with or install the equipment covered in this manual or any related equipment...

Страница 3: ...ALARM INDICATORS 16 TS SCM CONTROL SCREEN EVO 550 AND EVO 5000 17 STATUS INDICATOR TABLE 17 CONTROL INDICATOR TABLE 17 LEARN INDICATOR TABLE 17 TS SCM STATUS AND CONTROL SUMMARY SCREEN EVO 600 AND EV...

Страница 4: ...ENABLING DISABLING TS SCM 29 ENABLING TS SCM CHANNELS 29 DISABLING TS SCM CHANNELS 29 SCM ANNUAL FUNCTIONAL TESTING 29 CONTROL DRAWING 1 30 CONTROL DRAWING 2 32...

Страница 5: ...hazard may result if other openings are used WARNING All wiring from probes or sensors to the Tank Sentinel console must be run in conduit separate from all other wiring Failure to do so will create...

Страница 6: ...PSIG Mechanical Relief Valve Vacuum 10 Hg 5 PSIG Jumper Tubing Use only supplied vacuum tubing Vacuum Sensor Wiring Belden No 87761 0 12 OD to 400 ft Belden No 89182 0 31 OD to 500 ft maximum distanc...

Страница 7: ...containment group may not exceed the volume limits listed for the TS SCM NOTES DO NOT jumper tank interstitials with other tank interstitials or other containments DO NOT jumper containment areas of u...

Страница 8: ...nd non intrinsically safe non IS wiring in the same conduit NOTE TS SCM must be installed in accordance with the national electrical code ANSI NFPA 70 CEC or other applicable national or local codes N...

Страница 9: ...he TS SCM to the siphon check valve Secure the hose to the fittings using one of the supplied hose clamps at each end 7 Plumb the containment vacuum hose from the in line air filter barb to the contai...

Страница 10: ...rovided to the dry contact relay Earth Ground Black Locally sourced wire To source Voltage NOTE TS and VS are different source voltages For additional information refer to the manufacturers documentat...

Страница 11: ...f vacuum sensor wires are black and red connect the black wire to the negative terminal and the red wire to the positive terminal If vacuum sensor wires are blue and brown connect the blue wire to the...

Страница 12: ...r the Administrator access level when it is required NOTE Sites setups vary depending on products used and other equipment installed Setup information in the sections of this chapter depict a typical...

Страница 13: ...9 2 Next select which channel of the 4 20mA Module the TS SCM transducer is connect to 3 Next select the Relay where the TS SCM solenoid is connected to Relays are defined in the Relay section...

Страница 14: ...the signal is originated Enabled If yes will allow the channel to be mapped to another module Other modules may use this signal to trigger an event Active State If set to High a high signal level wil...

Страница 15: ...uum Sensor Service Type Secondary Containment Monitor RELAY MODULE The Relay Module contains eight separate relays called Relay Channels A channel is used to open and close an individual TS SCM soleno...

Страница 16: ...mA Input Module Channel Unleaded SCM Vacuum Sensor Channel 2 Name Premium Solenoid Valve Enabled Yes Type Solenoid Polarity Normal Logic OR Logic Physically Wired As Normally Open Number of inputs 1 I...

Страница 17: ...Unleaded Hook Signal Channel 2 Name Premium STP controller Enabled Yes Type Submersible Polarity Normal Logic OR Logic Physically Wired As Normally Open Number of inputs 2 Input 1 Type 4 20mA Input Mo...

Страница 18: ...up Name Parameter Name Parameter Value Power Supply RS 485 Enable Interface Yes TS TPI Enable Interface Yes Controllers A Number of Controllers 3 Controller 1 Name Unleaded Controller Enabled Yes Type...

Страница 19: ...ontainment area to the TS SCM Vacuum Sensor as specified by the 4 20mA Input Module channel assignments Example TS SCM Application Setup Group Name Parameter Name Parameter Value Secondary Containment...

Страница 20: ...arned amount of time Fail to Reach Vacuum The containment has not reached the learned level of vacuum within the learned amount of time High Vacuum The vacuum level of the containment has exceeded 9 H...

Страница 21: ...containment has not been learned Solenoid On Indicates whether the normally closed TS SCM solenoid is open or closed Vacuum Level A direct reading from the TS SCM Vacuum Sensor CONTROL INDICATORTABLE...

Страница 22: ...t Provides date and time of last pass or fail Learn Status Provides detail of the Learn mode of the containment NOTE For more information on alarms and troubleshooting refer to the Alarms chapter in t...

Страница 23: ...successfully completes pre operational testing Failure to perform these tests or ignoring any failed tests may prevent the TS SCM application from detecting a containment fault NOTE State and or local...

Страница 24: ...ed power on the vacuum pump Adjust the regulator to 6 5 7 Hg maximum Power the vacuum pump off 4 Remove the plug in the leak generator port on the TS SCM Connect the vacuum pump to this port 5 Power t...

Страница 25: ...in the Open position prior to energizing the STP NOTE If during this procedure the containment reaches 9 Hg which will cause the console to display a High Vacuum alarm and disable the containment High...

Страница 26: ...s the containment area to the TS SCM Vacuum Sensor as specified by the 4 20mA Input Module channel assignments Example TS SCM Application Setup Group Name Parameter Name Parameter Value Secondary Cont...

Страница 27: ...beginning Do not submerse or block the TS SCMCAL orifice while learning the containment The orifice must be kept free of dirt and debris WHENTO LEARN RE LEARN SCM installation and start up After repa...

Страница 28: ...ot Learned indicator will be active Refer to the Alarms chapter of this guide for information on troubleshooting any errors that are displayed 8 Once the containment has been successfully learned enab...

Страница 29: ...art the Learn Process and open the leak valve when prompted Close the leak valve after the Learn Process has completed Not Learned The containment has been programmed but the containment has never bee...

Страница 30: ...can be found below APPLICATION EVENT REPORTS Application Event Reports include any system warning pertaining to TS SCM equipment that occurred within the date range chosen by the user SCM REPORTS SCM...

Страница 31: ...ce while the console door is open NOTE Refer to the Important Safety Messages outlined in the beginning of this manual before performing any console maintenance NOTE If at any time while troubleshooti...

Страница 32: ...est on the containment using the TS SCM Control screen The STP will start only if necessary to evacuate the containment If the STP does not run to evacuate the containment verify programming G Verify...

Страница 33: ...is guide SCM ANNUAL FUNCTIONAL TESTING Perform a TS SCM Functional Test annually This test will verify that the TS SCM application will detect and alarm on a leak condition This test should be perform...

Страница 34: ...30 CONTROL DRAWING 1 EX CERTIFIED PRODUCT SCHEDULE DOCUMENT NO MODIFICATIONS PERMITTED WITHOUT APPROVAL FROM THE APPROPRIATE CERTIFICATION BODIES Exia 6L79 C US LISTED U L...

Страница 35: ...31 0539 II 1 G Ex ia Ga IIA DEMKO 05 ATEX 0430464X IECEx UL 05 0013X...

Страница 36: ...CIRCUITS RUN IN THE SAME CABLE CONDUIT MUST HAVE AT LEAST 0 25mm OF INSULATION 4 CAPACITANCE AND INDUCTANCE OF THE FIELD WIRING FROM THE INTRINSICALLY SAFE EQUIPMENT TO THE BARRIER SHALL BE CALCULATED...

Страница 37: ...HLD RED BLK 12 PWR A B GND 4 PWR A B GND 3 PWR A B GND 2 PWR A B GND 1 0539 Ex ia Ga IIA DEMKO 05 ATEX 0430464X IECEx UL 05 0013X II 1 G NOTES 1 THE MODEL EVO600 EVO6000 TS EXPC AND TS EXPC2 SHALL NOT...

Страница 38: ...INTENTIONALLY BLANK...

Страница 39: ...INTENTIONALLY BLANK...

Страница 40: ...000 0528 r7...

Отзывы: