SECONDARY CONTAINMENT MONITORING APPLICATION
Programming the TS-SCM application sets the parameters for TS-SCM and enables it to monitor a set
number of channels. Each containment area or group must be programmed separately on the console.
Parameter
Parameter Value
Enabled
Set to Yes.
Name
Should be a specific location or product type of the containment area.
Number of Containments
The number of TS-SCMs connected to the console.
Pump Shutdown on Alarm
If set to Yes, provides positive pump shutdown when the containment area is in
alarm.
Submersible Pump Channel
Maps the containment area to the specific pump control output channel.
Submersible Pump Module
Maps the containment area to a specific pump to provide pump on/off.
Transducer
Maps the containment area to the TS-SCM Vacuum Sensor as specified by the
4-20mA Input Module channel assignments.
Example: TS-SCM Application Setup:
Group Name
Parameter Name
Parameter Value
Secondary Containment Monitor
Number of Containments
3
Containment 1
Name
Unleaded Line Containment
Enabled
Yes
Pump Shutdown on Alarm
Yes
Submersible Pump Module
Relay Module (or Power Supply for TPI)
Submersible Pump Channel
Unleaded STP Controller
Transducer
Unleaded TS-SCM Vacuum Sensor
Containment 2
Name
Premium Line Containment
Enabled
Yes
Pump Shutdown on Alarm
Yes
Submersible Pump Module
Relay Module (or Power Supply for TPI)
Submersible Pump Channel
Premium Pump Controller
Transducer
Premium TS-SCM Vacuum Sensor
Containment 3
Name
Diesel Line Containment
Enabled
Yes
Pump Shutdown on Alarm
Yes
Submersible Pump Module
Relay Module (or Power Supply for TPI)
Submersible Pump Channel
Diesel Pump Controller
Transducer
Diesel TS-SCM Vacuum Sensor