6
8. Secure all containment boots, lids and caps. Clean pipe surfaces to clear debris or foreign objects
prior to tightening secondary test boots on secondary containment product or vapor return piping.
Make all jumper connections inside of dispenser sumps by using supplied hardware.
9. Inside the console, the TS-SCM solenoid wiring must enter the console from the explosion proof
rigid conduit through a designated knockout on the non-IS side of the barrier inside. Connect the
line to a single unused channel on the Relay Module (RLY). The solenoid should be wired to the
Normally Open (NO) contacts of the channel selected. Source voltage (110 VAC) will need to be
provided to the dry contact relay.
Earth Ground
Black
Locally sourced wire
To source Voltage
NOTE:
TS and VS are different source voltages. For additional information, refer to the manufacturers'
documentation included with the product.
WARNING
: If you use console power wires to provide power to a dry contact relay channel, ensure that
the console is positively shut down during installation and service. Failure to remove power may result in
damage to equipment, personal injury or even death.
10. The TS-SCM sensor wiring must enter the console in IS conduit through a knockout on the IS side
of the barrier. Secure each pair of sensor wires to a single channel on the 4-20mA Analog Input
Module. Always use the next available channel when wiring; for example, if Channels 1–3 are being
used, Channel 4 must be used next. Pay close attention to the polarity (+/-) of the wires.