4
INSTALLATION
Before starting installation, conduct a site survey to identify potential containment groups. Based on that
survey, plan out which STP sump the equipment will be installed in and how containment areas will be
grouped together.
NOTE:
For additional vacuum sensor safety information, refer to the manufacturers' documentation
included with the product.
WARNING
: Lockout and tag circuit breakers, and disconnect console power wiring before installing or
servicing any system wiring.
WARNING
: DO NOT make solenoid and/or sensor wiring connections with live power connected to the
console or any module.
WARNING
: Do not run intrinsically safe (IS) wiring and non-intrinsically safe (non-IS) wiring in the
same conduit.
NOTE:
TS-SCM must be installed in accordance with the national electrical code, ANSI/NFPA 70, CEC or
other applicable national or local codes.
NOTE:
Maximum torque on supplied hose clamps is 10.5 inch-lbs.
1. Pull all wiring through the conduits that will be used for the TS-SCM vacuum sensor and solenoid
valve. The intrinsically safe (IS) sensor wiring must be run in an IS conduit. The non-IS solenoid
wiring must be run in an approved explosion proof rigid metal conduit.
2. Mount the TS-SCM inside of the turbine containment area, supported by rigid, explosion proof
conduit. Then orientate the units to allow enough clearance to make the vacuum line connections
without stretching, kinking, or creating sharp bends in vacuum hoses. The TS-SCM cover is installed
with the label upwards.
TS-SCM/1
TS-SCM/2