15
TS-SCM APPLICATION
Programming the TS-SCM application sets the parameters for the TS-SCM and enables it to monitor a set
number of channels. Each containment area or group must be programmed separately on the console.
Parameter
Parameter Value
Enabled
Set to
Yes
.
Name
Should be a specific location or product type of the containment area.
Number of Containments
The number of TS-SCMs connected to the console.
Pump Shutdown on Alarm
If set to
Yes
, provides positive pump shutdown when the containment
area is in alarm.
Submersible Pump Channel Maps the containment area to the specific pump control output channel.
Submersible Pump Module Maps the containment area to a specific pump to provide pump on/off.
Transducer
Maps the containment area to the TS-SCM Vacuum Sensor as specified
by the 4-20mA Input Module channel assignments.
Example: TS-SCM Application Setup
Group Name
Parameter Name
Parameter Value
Secondary Containment Monitor Number of Containments
3
Containment 1
Name Unleaded Line Containment
Enabled Yes
Pump Shutdown on Alarm Yes
Submersible Pump Module Relay Module (or Power Supply for
TPI)
Submersible Pump Channel Unleaded STP Controller
Transducer Unleaded SCM Vacuum Sensor
Containment 2
Name Premium Line Containment
Enabled Yes
Pump Shutdown on Alarm Yes
Submersible Pump Module Relay Module (or Power Supply for
TPI)
Submersible Pump Channel Premium Pump Controller
Transducer Premium SCM Vacuum Sensor
Containment 3
Name Diesel Line Containment
Enabled Yes
Pump Shutdown on Alarm Yes
Submersible Pump Module Relay Module (or Power Supply for
TPI)
Submersible Pump Channel Diesel Pump Controller
Transducer Diesel SCM Vacuum Sensor