background image

15

TS-SCM APPLICATION

Programming the TS-SCM application sets the parameters for the TS-SCM and enables it to monitor a set 

number of channels. Each containment area or group must be programmed separately on the console.

Parameter

Parameter Value

Enabled

Set to 

Yes

.

Name

Should be a specific location or product type of the containment area.

Number of Containments

The number of TS-SCMs connected to the console.

Pump Shutdown on Alarm

If set to 

Yes

, provides positive pump shutdown when the containment 

area is in alarm.

Submersible Pump Channel Maps the containment area to the specific pump control output channel.
Submersible Pump Module Maps the containment area to a specific pump to provide pump on/off.

Transducer

Maps the containment area to the TS-SCM Vacuum Sensor as specified 

by the 4-20mA Input Module channel assignments.

Example: TS-SCM Application Setup

Group Name

Parameter Name

Parameter Value

Secondary Containment Monitor Number of Containments

3

 

Containment 1

Name Unleaded Line Containment

Enabled Yes

Pump Shutdown on Alarm Yes

Submersible Pump Module Relay Module (or Power Supply for 

TPI)

Submersible Pump Channel Unleaded STP Controller

Transducer Unleaded SCM Vacuum Sensor

Containment 2

Name Premium Line Containment

Enabled Yes

Pump Shutdown on Alarm Yes

Submersible Pump Module Relay Module (or Power Supply for 

TPI)

Submersible Pump Channel Premium Pump Controller

Transducer Premium SCM Vacuum Sensor

Containment 3

Name Diesel Line Containment

Enabled Yes

Pump Shutdown on Alarm Yes

Submersible Pump Module Relay Module (or Power Supply for 

TPI)

Submersible Pump Channel Diesel Pump Controller

Transducer Diesel SCM Vacuum Sensor

Содержание TS-SCM

Страница 1: ...TS SCM SECONDARY CONTAINMENT MONITORING INSTALLATION GUIDE...

Страница 2: ...evere injury or death if you do not follow standard industry practices and the instructions in this manual Before you work with or install the equipment covered in this manual or any related equipment...

Страница 3: ...ALARM INDICATORS 16 TS SCM CONTROL SCREEN EVO 550 AND EVO 5000 17 STATUS INDICATOR TABLE 17 CONTROL INDICATOR TABLE 17 LEARN INDICATOR TABLE 17 TS SCM STATUS AND CONTROL SUMMARY SCREEN EVO 600 AND EV...

Страница 4: ...ENABLING DISABLING TS SCM 29 ENABLING TS SCM CHANNELS 29 DISABLING TS SCM CHANNELS 29 SCM ANNUAL FUNCTIONAL TESTING 29 CONTROL DRAWING 1 30 CONTROL DRAWING 2 32...

Страница 5: ...hazard may result if other openings are used WARNING All wiring from probes or sensors to the Tank Sentinel console must be run in conduit separate from all other wiring Failure to do so will create...

Страница 6: ...PSIG Mechanical Relief Valve Vacuum 10 Hg 5 PSIG Jumper Tubing Use only supplied vacuum tubing Vacuum Sensor Wiring Belden No 87761 0 12 OD to 400 ft Belden No 89182 0 31 OD to 500 ft maximum distanc...

Страница 7: ...containment group may not exceed the volume limits listed for the TS SCM NOTES DO NOT jumper tank interstitials with other tank interstitials or other containments DO NOT jumper containment areas of u...

Страница 8: ...nd non intrinsically safe non IS wiring in the same conduit NOTE TS SCM must be installed in accordance with the national electrical code ANSI NFPA 70 CEC or other applicable national or local codes N...

Страница 9: ...he TS SCM to the siphon check valve Secure the hose to the fittings using one of the supplied hose clamps at each end 7 Plumb the containment vacuum hose from the in line air filter barb to the contai...

Страница 10: ...rovided to the dry contact relay Earth Ground Black Locally sourced wire To source Voltage NOTE TS and VS are different source voltages For additional information refer to the manufacturers documentat...

Страница 11: ...f vacuum sensor wires are black and red connect the black wire to the negative terminal and the red wire to the positive terminal If vacuum sensor wires are blue and brown connect the blue wire to the...

Страница 12: ...r the Administrator access level when it is required NOTE Sites setups vary depending on products used and other equipment installed Setup information in the sections of this chapter depict a typical...

Страница 13: ...9 2 Next select which channel of the 4 20mA Module the TS SCM transducer is connect to 3 Next select the Relay where the TS SCM solenoid is connected to Relays are defined in the Relay section...

Страница 14: ...the signal is originated Enabled If yes will allow the channel to be mapped to another module Other modules may use this signal to trigger an event Active State If set to High a high signal level wil...

Страница 15: ...uum Sensor Service Type Secondary Containment Monitor RELAY MODULE The Relay Module contains eight separate relays called Relay Channels A channel is used to open and close an individual TS SCM soleno...

Страница 16: ...mA Input Module Channel Unleaded SCM Vacuum Sensor Channel 2 Name Premium Solenoid Valve Enabled Yes Type Solenoid Polarity Normal Logic OR Logic Physically Wired As Normally Open Number of inputs 1 I...

Страница 17: ...Unleaded Hook Signal Channel 2 Name Premium STP controller Enabled Yes Type Submersible Polarity Normal Logic OR Logic Physically Wired As Normally Open Number of inputs 2 Input 1 Type 4 20mA Input Mo...

Страница 18: ...up Name Parameter Name Parameter Value Power Supply RS 485 Enable Interface Yes TS TPI Enable Interface Yes Controllers A Number of Controllers 3 Controller 1 Name Unleaded Controller Enabled Yes Type...

Страница 19: ...ontainment area to the TS SCM Vacuum Sensor as specified by the 4 20mA Input Module channel assignments Example TS SCM Application Setup Group Name Parameter Name Parameter Value Secondary Containment...

Страница 20: ...arned amount of time Fail to Reach Vacuum The containment has not reached the learned level of vacuum within the learned amount of time High Vacuum The vacuum level of the containment has exceeded 9 H...

Страница 21: ...containment has not been learned Solenoid On Indicates whether the normally closed TS SCM solenoid is open or closed Vacuum Level A direct reading from the TS SCM Vacuum Sensor CONTROL INDICATORTABLE...

Страница 22: ...t Provides date and time of last pass or fail Learn Status Provides detail of the Learn mode of the containment NOTE For more information on alarms and troubleshooting refer to the Alarms chapter in t...

Страница 23: ...successfully completes pre operational testing Failure to perform these tests or ignoring any failed tests may prevent the TS SCM application from detecting a containment fault NOTE State and or local...

Страница 24: ...ed power on the vacuum pump Adjust the regulator to 6 5 7 Hg maximum Power the vacuum pump off 4 Remove the plug in the leak generator port on the TS SCM Connect the vacuum pump to this port 5 Power t...

Страница 25: ...in the Open position prior to energizing the STP NOTE If during this procedure the containment reaches 9 Hg which will cause the console to display a High Vacuum alarm and disable the containment High...

Страница 26: ...s the containment area to the TS SCM Vacuum Sensor as specified by the 4 20mA Input Module channel assignments Example TS SCM Application Setup Group Name Parameter Name Parameter Value Secondary Cont...

Страница 27: ...beginning Do not submerse or block the TS SCMCAL orifice while learning the containment The orifice must be kept free of dirt and debris WHENTO LEARN RE LEARN SCM installation and start up After repa...

Страница 28: ...ot Learned indicator will be active Refer to the Alarms chapter of this guide for information on troubleshooting any errors that are displayed 8 Once the containment has been successfully learned enab...

Страница 29: ...art the Learn Process and open the leak valve when prompted Close the leak valve after the Learn Process has completed Not Learned The containment has been programmed but the containment has never bee...

Страница 30: ...can be found below APPLICATION EVENT REPORTS Application Event Reports include any system warning pertaining to TS SCM equipment that occurred within the date range chosen by the user SCM REPORTS SCM...

Страница 31: ...ce while the console door is open NOTE Refer to the Important Safety Messages outlined in the beginning of this manual before performing any console maintenance NOTE If at any time while troubleshooti...

Страница 32: ...est on the containment using the TS SCM Control screen The STP will start only if necessary to evacuate the containment If the STP does not run to evacuate the containment verify programming G Verify...

Страница 33: ...is guide SCM ANNUAL FUNCTIONAL TESTING Perform a TS SCM Functional Test annually This test will verify that the TS SCM application will detect and alarm on a leak condition This test should be perform...

Страница 34: ...30 CONTROL DRAWING 1 EX CERTIFIED PRODUCT SCHEDULE DOCUMENT NO MODIFICATIONS PERMITTED WITHOUT APPROVAL FROM THE APPROPRIATE CERTIFICATION BODIES Exia 6L79 C US LISTED U L...

Страница 35: ...31 0539 II 1 G Ex ia Ga IIA DEMKO 05 ATEX 0430464X IECEx UL 05 0013X...

Страница 36: ...CIRCUITS RUN IN THE SAME CABLE CONDUIT MUST HAVE AT LEAST 0 25mm OF INSULATION 4 CAPACITANCE AND INDUCTANCE OF THE FIELD WIRING FROM THE INTRINSICALLY SAFE EQUIPMENT TO THE BARRIER SHALL BE CALCULATED...

Страница 37: ...HLD RED BLK 12 PWR A B GND 4 PWR A B GND 3 PWR A B GND 2 PWR A B GND 1 0539 Ex ia Ga IIA DEMKO 05 ATEX 0430464X IECEx UL 05 0013X II 1 G NOTES 1 THE MODEL EVO600 EVO6000 TS EXPC AND TS EXPC2 SHALL NOT...

Страница 38: ...INTENTIONALLY BLANK...

Страница 39: ...INTENTIONALLY BLANK...

Страница 40: ...000 0528 r7...

Отзывы: