PROGRAMMING
The following instructions cover TS-SCM programming only. Administrator privileges are necessary
to program the TS-SCM application. (For console programming instructions or information about
obtaining Administrator access level, see the list of programming manuals in the “ADDITIONAL
DOCUMENTATION” section.)
Access the console, and open the Setup Menu. Go to each of the following sections, and adjust the
TS-SCM parameters accordingly. You will be prompted to enter the Administrator access level when it is
required.
NOTE:
Sites setups vary depending on products used and other equipment installed. Setup information in
the sections of this chapter depict a typical site and are meant as examples only.
EVO™ 600 AND EVO™ 6000 PROGRAMMING
When you program a containment you want to monitor, obtain the following information:
• The pump that is providing the vacuum.
• The 4-20 mA channel the vacuum sensor transducer is connected to.
• The relay that is controlling the solenoid.
From Fuel Management>Secondary Containment Moni:
1. Select the pump the TS-SCM Module is paired with. Pumps are defined in the Pump section.
Where the pumps are defined:
Содержание TS-SCM