3
Individual containment sections of a given product pipeline may be jumpered together via a vacuum line
to form one larger single containment. An example of ‘jumpered’ containment spaces is the secondary
containment layer of product piping from the turbine containment to the first dispenser, and then jumpered
to the secondary containment layer of the same product piping on the other side leading to a second
dispenser containment area.
Several containment areas may be grouped together and used with a single TS-SCM. No more than four
(4) TS-SCM groups should be used per pump siphon. The combination of any containment group may not
exceed the volume limits listed for the TS-SCM.
NOTES
:
• DO NOT jumper tank interstitials with other tank interstitials or other containments.
• DO NOT jumper containment areas of unlike product pipelines together.
• If grouping multiple containment areas together, the installer will need to purchase and use the
vacuum hose, fittings, and clamps to secure the connection as specified by FFS.
• Both intrinsically safe and explosion proof conduits need to be available inside of the turbine
containment for the TS-SCM.
• Refer to the FFS product catalog for the current TS-SCM configurations offered.
SCM DIMENSIONS
TS-SCM/1
TS-SCM/2
TS-SCM Side View
5.0"
6.0"
5.25"
5.25"
5.7"
6.5"
2.00"
4.00"
4.00"
NOTE:
The TS-SCM 1 can monitor one containment group, and the TS-SCM 2 can monitor two
containment groups.