3 Block MEASURED VARIABLES

Device Functions Proline Promass 83 

3.3

Group 

SPECIAL-UNITS

3.3.1

Function group ARBITRARY UNIT

MEASURED 

VARIABLES

A

Ÿ

MEASURING VALUES

AAA

 

SYSTEM UNITS

ACA

 

SPECIAL-UNITS

AEA

Ÿ

ARBITRARY UNIT

060

Function description

MEASURED VARIABLES 

o

 SPECIAL-UNITS 

o

 ARBITRARY UNIT

Use this function group to define a free selectable unit for mass, mass flow, volume, volume flow, density and 
concentration (optional).

TEXT ARBITRARY MASS
(0600)

Use this function to enter a text for the selectable mass unit / mass flow unit. You define 
only the text, the unit of time is provided from a choice of options (s, min, h, day).

User input:

xxxxxxx (max. 4 characters) 
Valid characters are A-Z, 0-9, +, 

-

, decimal point, white space or underscore

Factory setting:

“_ _ _ _” (No text)

Example:
If your text entry is “CENT” (for centner), this text string appears on the display complete 
with the unit of time, e.g. “CENT/min”:
CENT = Mass (text input)
CENT / min = Mass flow as shown (on the display)

FACTOR ARBITRARY 
MASS
(0601)

Use this function to define a quantity factor (without time) for the selectable mass-/ 
mass flow unit. The mass unit on which this factor is based is one kilogram.

User input:

7-digit floating-point number

Factory setting:

1

Reference quantity:

kg

Example:
One centner is equivalent to 50 kg  

o

0.02 centner = 1 kg

User input: 0.02

Содержание Proline Promass 83 E

Страница 1: ...Description of Device Functions Issue Rev 0 2 12 12 Bulletin MN0M023 Proline Promass 83 E F O The Most Trusted Name In Measurement Coriolis Mass Flowmeters Valid as of version V 3 00 XX device software ...

Страница 2: ...Issue Rev 0 2 12 12 Page 2 MN0M023 This Page Intentionally Left Blank ...

Страница 3: ...3 3 2 Group SYSTEM UNITS 17 3 2 1 Function group CONFIGURATION 17 3 2 2 Function group ADDITIONAL CONFIGURATION 20 3 3 Group SPECIAL UNITS 22 3 3 1 Function group ARBITRARY UNIT 22 4 Block QUICK SETUP 25 4 1 Setup Commissioning 27 4 2 Pulsating flow Setup menu 29 4 3 Gas measurement Setup menu 31 4 4 Batching Setup menu 32 4 5 Data back up transfer 34 5 Block USER INTERFACE 35 5 1 Group CONTROL 36...

Страница 4: ...ion group OPERATION 117 8 2 3 Function group INFORMATION 118 9 Block BASIC FUNCTION 119 9 1 Group HART 120 9 1 1 Function group CONFIGURATION 120 9 1 2 Function group INFORMATION 121 9 2 Group PROCESS PARAMETER 122 9 2 1 Function group CONFIGURATION 122 9 2 2 Function group EPD PARAMETER 125 9 2 3 Function group REFERENCE PARAMETER 127 9 2 4 Function group ADJUSTMENT 129 9 2 5 Function group PRESS...

Страница 5: ...STEM 180 11 1 1 Function group CONFIGURATION 180 11 1 2 Function group OPERATION 183 11 2 Group VERSION INFO 185 11 2 1 Function group DEVICE 185 11 2 2 Function group SENSOR 185 11 2 3 Function group AMPLIFIER 186 11 2 4 Function group F CHIP 187 11 2 5 Function group I O MODULE 187 11 2 6 Function groups INPUT OUTPUT 1 4 188 12 Factory settings 189 12 1 SI units not for USA and Canada 189 12 1 1...

Страница 6: ... Table of Contents Device Functions Proline Promass 83 Registered trademarks HART Registered trademark of HART Communication Foundation Austin USA HistoROM S DAT T DAT F CHIP Registered trademarks of Endress Hauser Flowtec AG Reinach CH ...

Страница 7: ...the function you need 1 All blocks available and their related groups are illustrated on page 10 Select the block or the group within the block which you need for your application and use the page reference to locate the information corresponding to the next level 2 The page in question contains a graphic showing of the block with all its subordinate groups function groups and functions Select the...

Страница 8: ...e detailed selection of the operation options in the higher order group The function groups in the CONTROL group for example include BASIC CONFIGURATION UN LOCKING OPERATION etc 2 1 4 Functions 0000 0001 0002 etc Each function group consists of one or more functions The functions are used to operate and configure the device Numerical values can be entered or parameters selected and saved The funct...

Страница 9: ...ode starting with an A _ _ the codes of the groups in block B start with a B _ _ etc The other two letters are for identifying the group within the respective block Function groups The code consists of three digits 000 001 100 etc Functions The code consists of four digits 0000 0001 0201 etc The first three digits are the same as the code for the function group The last digit in the code is a coun...

Страница 10: ...o see p 57 p TOTALIZER 3 DAC o see p 57 HANDLING TOTALIZER DJA o see p 60 OUTPUTS E o CURRENT OUTPUT 1 EAA o see p 62 see p 61 CURRENT OUTPUT 2 EAB o see p 62 p CURRENT OUTPUT 3 EAC o see p 62 PULSE FREQ OUTPUT 1 ECA o see p 74 PULSE FREQ OUTPUT 2 ECB o see p 74 RELAY OUTPUT 1 EGA o see p 101 RELAY OUTPUT 2 EGB o see p 101 INPUTS F o STATUS INPUT FAA o see p 112 see p 111 CURRENT INPUT FCA o see p...

Страница 11: ...DENSITY 0005 p 12 TARGET VOLUME FLOW 0023 p 13 PLATO 0034 p 16 UNIT VOLUME 0403 p 18 UNIT LENGTH 0424 p 21 FACTOR ARB VOLUME 0603 p 23 CORRECTED VOL FLOW 0004 p 12 TARGET VOLUME FLOW 0022 p 13 API 0033 p 15 UNIT VOLUME FLOW 0402 p 18 UNIT TEMPERATURE 0422 p 21 TEXT ARB VOLUME 0602 p 23 VOLUME FLOW 0001 p 12 TARGET MASS FLOW 0021 p 13 BAUME 0031 p 15 UNIT MASS 0401 p 17 UNIT REFERENCE DENSITY 0421 ...

Страница 12: ...e measured mass flow and the reference density of the fluid density at reference temperature measured or fixed entry Display 5 digit floating point number including unit and sign e g 1 3549 Nm3 h 7 9846 scm day etc DENSITY 0005 The currently measured density or its specific gravity appears on the display Display 5 digit floating point number incl unit corresponds to 0 1000 to 6 0000 kg dm3 e g 1 2...

Страница 13: ... MASS 2D or MASS 3D In this function the currently measured mass flow of the target fluid is displayed as a of the overall mass flow Target fluid carried material e g lime powder Display 5 digit floating point number including unit and sign TARGET VOLUME FLOW 0022 Note This function is not available unless one of the following was selected in the function DENSITY FUNCTION 7000 see page 141 MASS VO...

Страница 14: ...igit floating point number including unit and sign CARRIER MASS FLOW 0026 Note This function is not available unless one of the following was selected in the function DENSITY FUNCTION 7000 see page 141 MASS VOLUME FLEXIBLE and in the function MODE 7010 see page 144 the selection MASS 2D or MASS 3D Use this function to display the currently measured mass flow of the carrier fluid as a of the overal...

Страница 15: ...e this function to display the currently measured corrected volume flow of the carrier fluid Carrier fluid transporting liquid e g water Display 5 digit floating point number including unit and sign BLACK LIQUOR 0030 Note This function is not available unless BLACK LIQUOR was selected in the DENSITY FUNCTION function 7000 see page 141 The concentration in BLACK LIQUOR is displayed Display 5 digit ...

Страница 16: ...mber incl units BRIX 0036 Note This function is not available unless BRIX was selected in the DENSITY FUNCTION function 7000 see page 141 The concentration in BRIX is displayed Display 5 digit floating point number incl units OTHERS 0037 Note This function is not available unless FLEXIBLE was selected in the DENSITY FUNCTION function 7000 see page 141 and this function is not available unless OTHE...

Страница 17: ...oz min oz h oz day pound o lb s lb min lb h lb day ton o ton s ton min ton h ton day For arbitrary units see function TEXT ARBITRARY MASS on page 22 _ _ _ _ o _ _ _ _ s _ _ _ _ min _ _ _ _ h _ _ _ _ day Factory setting Country dependent kg h or US lb min Note If you defined a unit of mass in the ARBITRARY UNIT 060 function group see page 22 the unit in question is shown here UNIT MASS 0401 Use thi...

Страница 18: ... tanks 55 0 gal bbl o bbl s bbl min bbl h bbl day Imperial Gallon o gal s gal min gal h gal day Mega gallon o Mgal s Mgal min Mgal h Mgal day Barrel beer 36 0 gal bbl o bbl s bbl min bbl h bbl day Barrel petrochemicals 34 97 gal bbl o bbl s bbl min bbl h bbl day For arbitrary units see function TEXT ARBITRARY VOLUME on page 23 _ _ _ _ o _ _ _ _ s _ _ _ _ min _ _ _ _ h _ _ _ _ day Factory setting C...

Страница 19: ...cut off Options Metric Nl s Nl min Nl h Nl day Nm3 s Nm3 min Nm3 h Nm3 day US Sm3 s Sm3 min Sm3 h Sm3 day Scf s Scf min Scf h Scf day Factory setting Nm3 h UNIT CORRECTED VOLUME 0405 Use this function to select the unit for displaying the corrected volume The unit you select here is also valid for Pulse value e g Nm3 p Options Metric Nm3 Nl US Sm3 Scf Factory setting Nm3 Note The unit of the total...

Страница 20: ... o g cm3 g cc kg dm3 kg l kg m3 SD 4 C SD 15 C SD 20 C SG 4 C SG 15 C SG 20 C US o lb ft3 lb gal lb bbl normal fluids lb bbl beer lb bbl petrochemicals lb bbl filling tanks Imperial o lb gal lb bbl beer lb bbl petrochemicals Factory setting kg l SD Specific Density SG Specific Gravity The specific density is the ratio of fluid density to water density at water temperature 4 15 20 C UNIT REFERENCE ...

Страница 21: ... C Celsius K Kelvin F Fahrenheit R Rankine Factory setting C UNIT LENGTH 0424 Use this function to select the unit for displaying the length of the nominal diameter The unit you select here is valid for Nominal diameter of sensor function NOMINAL DIAMETER 6804 on page 135 Options MILLIMETER INCH Factory setting MILLIMETER UNIT PRESSURE 0426 Use this function to select the unit for pressure The uni...

Страница 22: ...u define only the text the unit of time is provided from a choice of options s min h day User input xxxxxxx max 4 characters Valid characters are A Z 0 9 decimal point white space or underscore Factory setting _ _ _ _ No text Example If your text entry is CENT for centner this text string appears on the display complete with the unit of time e g CENT min CENT Mass text input CENT min Mass flow as ...

Страница 23: ...lectable unit The volume unit on which this factor is based is one liter User input 7 digit floating point number Factory setting 1 Reference quantity Liter Example The volume of a glass is 0 5 l o 2 glasses 1 liter User input 2 TEXT ARBITRARY DENSITY 0604 Use this function to enter a text for the selectable density unit User input xxxxxxx max 4 characters Valid characters are A Z 0 9 decimal poin...

Страница 24: ...text Example Enter text HFCS for High Fructose Corn Syrup FACTOR ARBITRARY CONCENTRATION 0607 Note This function is not available unless the optional software package CONCENTRATION is installed and an option selected in the function DENSITY FUNCTION 7000 see page 141 Use this function to define a factor for the selectable concentration unit see function TEXT ARBITRARY CONCENTRATION 0606 User input...

Страница 25: ...rmation on Setup menus please refer to the Operating Instructions Proline Promass 83 BA 059D 06 en QUICK SETUP PULSATING FLOW 1003 Use this function to start the application specific Setup menu for pulsating flow Options YES NO Factory setting NO Note You will find a flowchart of the PULSATING FLOW setup menu on page 29 For more information on Setup menus please refer to the Operating Instructions...

Страница 26: ...ter in a transmitter DAT T DAT or to load the parameter settings from the T DAT into the EEPROM manual safety function Application examples After commissioning the current measuring point parameters can be saved to the T DAT as a backup If the transmitter is replaced for some reason the data from the T DAT can be loaded into the new transmitter EEPROM Options CANCEL SAVE from EEPROM to T DAT LOAD ...

Страница 27: ...s mode Meas mode Time constant Time constant Failsafe mode Failsafe mode Failsafe mode Assign Freq output End value freq Value F Low Value F High Output signal Assign Pulse output Pulse value Pulse width Output signal Operation Mode Frequency Pulse Automatic parameterization of the display Reference Calculated Fix Density Density Unit Ref Density Exp Coeff Lin Exp Coeff SQR Reference temp Volume f...

Страница 28: ...or mass volume and corrected volume is derived from the corresponding flow unit o The YES option remains visible until all the units have been configured NO is the only option displayed when no further units are available p Only the outputs not yet configured in the current Setup are offered for selection in each cycle q The YES option remains visible until all the outputs have been configured NO ...

Страница 29: ...utputs have been configured NO is the only option displayed when no further outputs are available E E 3002 3002 3002 4200 4225 8005 6400 6402 6403 6404 4206 4208 4004 4005 B 2002 1003 Esc E XXX XXX XX Yes Yes No No n Configure another totalizer o Current output n Freq Puse output n Selection of output type Quit m Totalizer 2 Totalizer 1 Totalizer 3 Selection totalizer Quit Totalizer mode DAA Total...

Страница 30: ...CURRENT OUTPUT 1 n 4004 MEASURING MODE PULSATING FLOW see p 68 4005 TIME CONSTANT 1 second see p 70 Select the signal type FREQ PULSE OUTPUT 1 2 operating mode FREQUENCY 4206 MEASURING MODE PULSATING FLOW see p 79 4208 TIME CONSTANT 0 seconds see p 84 Select the signal type FREQ PULSE OUTPUT 1 2 operating mode PULSE 4225 MEASURING MODE PULSATING FLOW see p 87 Other settings 8005 ALARM DELAY 0 seco...

Страница 31: ...tion 6420 EMPTY PIPE DETECTION No entry possible the selection changes automatically to OFF see p 125 6400 ASSIGN LOW FLOW CUT OFF For gas measurement we recommend to switch off the low flow cut off OFF see p 122 6402 ON VALUE LOW FLOW CUT OFF If you don t switch off the low flow cut off 0 0000 see p 122 6403 OFF VALUE LOW FLOW CUT OFF If you don t switch off the low flow cut off 50 see p 122 E E ...

Страница 32: ... E ON Value Low flow cut off Flow damping Pressure shock suppression Batch Selector Batch Name Batch Quantity Fix Compensation Quantity Assign Relay Terminal No Max Batch Time QS Batching Dosing YES NO Batch Supervision YES NO Autom Configuration Display Automatic parameterization of the display Quick Setup Quit Quick Setup Locked Access Customer PRESET Batch quantity Relay 1 Relay 2 Select Output...

Страница 33: ...NG or the PULSATING FLOW Setup Settings for the Batching Setup menu Fct code Function name Suggested settings Description Call up through the function matrix B QUICK SETUP QUICK SETUP BATCHING DOSING see p 25 1005 QUICK SETUP BATCHING DOSING YES see p 26 Settings functions with a gray background are set automatically 6400 ASSIGN LOW FLOW CUT OFF Mass see p 122 6402 ON VALUE LOW FLOW CUT OFF Table ...

Страница 34: ...measuring points Note Installing and removing the T DAT o Operating Instructions of the Promass 83 BA059D a0001221 en Data storage transmission with T DAT SAVE LOAD Notes on the LOAD and SAVE options LOAD Data are transmitted from the T DAT to the EEPROM Note Previously saved settings on the EEPROM are deleted This selection is available only if the T DAT contains valid data This selection can be ...

Страница 35: ... p 36 DEF PRIVATE CODE 2021 p 38 100 VALUE 2201 p 41 100 VALUE 2221 p 43 100 VALUE 2401 p 45 100 VALUE 2421 p 48 100 VALUE 2601 p 51 100 VALUE 2621 p 54 LANGUAGE 2000 p 36 ACCESS CODE 2020 p 38 TEST DISPLAY 2040 p 39 ASSIGN 2200 p 40 ASSIGN 2220 p 42 ASSIGN 2400 p 44 ASSIGN 2420 p 47 ASSIGN 2600 p 50 ASSIGN 2620 p 53 Function groups BASIC CONFIG 200 p 36 UN LOCKING 202 p 38 OPERATION 204 p 39 CONF...

Страница 36: ...UGUESE Language group EAST EU SCAND ENGLISH NORSK SVENSKA SUOMI POLISH RUSSIAN CZECH Language group ASIA ENGLISH BAHASA INDONESIA JAPANESE syllabary Language group CHINA ENGLISH CHINESE Factory setting Country dependent page 190 Note If you press the O S keys at startup the language defaults to ENGLISH You can change the language group via the configuration software FieldCare Please do not hesitat...

Страница 37: ...er input 10 100 Factory setting 50 BACKLIGHT 2004 Use this function to optimize the backlight to suit local operating conditions User input 0 100 Note Entering the value 0 means that the backlight is switched off The display then no longer emits any light i e the display texts can no longer be read in the dark Factory setting 50 Function description USER INTERFACE o CONTROL o BASIC CONFIGURATION ...

Страница 38: ...within 60 seconds following automatic return to the HOME position You can also disable programming in this function by entering any number other than the defined private code The Endress Hauser service organization can be of assistance if you mislay your personal code DEFINE PRIVATE CODE 2021 Use this function to specify a personal code for enabling programming in the function ACCESS CODE User inp...

Страница 39: ... OFF ON Factory setting OFF Test sequence 1 Start the test by selecting ON 2 All pixels of the main line additional line and information line are darkened for minimum 0 75 second 3 Main line additional line and information line show an 8 in each field for minimum 0 75 seconds 4 Main line additional line and information line show a 0 in each field for minimum 0 75 seconds 5 Main line additional lin...

Страница 40: ...ing MASS FLOW Advanced options with optional software package BATCHING BATCH NAME BATCH 1 or BEER 330 etc BATCH QUANTITY overall quantity to be batched BATCH COUNTER batching processes carried out BATCH SUM effective total batching quantity Note The options given in the BATCHING software package always refer to the batching selected BATCH 1 BATCH 2 etc in the BATCH SELECTOR function page 147 Examp...

Страница 41: ...d in the ASSIGN function 2200 MASS FLOW IN VOLUME FLOW IN CORRECTED VOLUME FLOW IN Use this function to define the flow value to be shown on the display as the 100 value User input 5 digit floating point number Factory setting 10 kg s 10 l s or 10 Nl s FORMAT 2202 Use this function to define the maximum number of places after the decimal point displayed for the reading in the main line Options XXX...

Страница 42: ... options with optional software package BATCHING BATCH NAME BATCH 1 or BEER 330 etc BATCH QUANTITY overall quantity to be batched BATCH COUNTER batching processes carried out BATCH SUM effective total batching quantity Note The options given in the BATCHING software package always refer to the batching selected BATCH 1 BATCH 2 etc in the BATCH SELECTOR function page 147 Example If BATCH 1 was sele...

Страница 43: ...input 5 digit floating point number Factory setting 10 kg s 10 l s or 10 Nl s FORMAT 2222 Use this function to define the maximum number of places after the decimal point for the second value displayed in the main line Options XXXXX XXXX X XXX XX XX XXX X XXXX Factory setting X XXXX Note Note that this setting only affects the reading as it appears on the display it has no influence on the accurac...

Страница 44: ...ing normal operation Options standard OFF MASS FLOW MASS FLOW IN VOLUME FLOW VOLUME FLOW IN CORRECTED VOLUME FLOW CORRECTED VOLUME FLOW IN DENSITY REFERENCE DENSITY TEMPERATURE MASS FLOW BARGRAPH IN VOLUME FLOW BARGRAPH IN CORRECTED VOLUME FLOW BARGRAPH IN ACTUAL CURRENT 1 3 ACTUAL FREQUENCY 1 2 TOTALIZER 1 3 TAG NAME ACTUAL CURRENT INPUT Factory setting TOTALIZER 1 Advanced options with optional ...

Страница 45: ... VOLUME FLOW BLACK LIQUOR BAUME API PLATO BALLING BRIX OTHERS _ _ _ _ flexible concentration Advanced options with optional software package ADVANCED DIAGNOSIS MASS FLOW DEVIATION DENSITY DEVIATION REFERENCE DENSITY DEVIATION TEMPERATURE DEVIATION TUBE DAMPING DEVIATION ELECTRODYNAMIC SENSOR DEVIATION OPERATING FREQUENCY FLUCTUATION DEVIATION TUBE DAMPING FLUCTUATION DEVIATION 100 VALUE 2401 Note ...

Страница 46: ...ending on this setting and the engineering unit In such instances an arrow appears on the display between the measuring value and the engineering unit e g 1 2 o kg h indicating that the measuring system is computing with more decimal places than can be shown on the display DISPLAY MODE 2403 Note This function is not available unless one of the following was selected in the ASSIGN function 2400 MAS...

Страница 47: ... MASS FLOW BARGRAPH IN VOLUME FLOW BARGRAPH IN CORRECTED VOLUME FLOW BARGRAPH IN ACTUAL CURRENT 1 3 ACTUAL FREQUENCY 1 2 TOTALIZER 1 3 TAG NAME ACTUAL CURRENT INPUT Factory setting OFF Advanced options with optional software package BATCHING BATCH NAME BATCH 1 or BEER 330 etc BATCH QUANTITY overall quantity to be batched BATCH COUNTER batching processes carried out BATCH SUM effective total batchi...

Страница 48: ...essage is generated The message in question appears on the display Fault message identified by a lightning icon If ON was selected in the ACKNOWLEDGE FAULTS 8004 function multiplex mode is continued as soon as the fault has been acknowledged and is no longer active If OFF was selected in the ACKNOWLEDGE FAULTS 8004 function multiplex mode is continued as soon as the fault is no longer active Notic...

Страница 49: ...d depending on this setting and the engineering unit In such instances an arrow appears on the display between the measuring value and the engineering unit e g 1 2 o kg h indicating that the measuring system is computing with more decimal places than can be shown on the display DISPLAY MODE 2423 Note This function is not available unless one of the following was selected in the ASSIGN function 242...

Страница 50: ...0 In this function a value to be displayed is assigned to the information line bottom line in the local display This value is displayed during normal operation Options OFF MASS FLOW MASS FLOW IN VOLUME FLOW VOLUME FLOW IN CORRECTED VOLUME FLOW CORRECTED VOLUME FLOW IN DENSITY REFERENCE DENSITY TEMPERATURE MASS FLOW BARGRAPH IN VOLUME FLOW BARGRAPH IN CORRECTED VOLUME FLOW BARGRAPH IN ACTUAL CURREN...

Страница 51: ...E FLOW CARRIER VOLUME FLOW CORRECTED CARRIER VOLUME FLOW BLACK LIQUOR BAUME API PLATO BALLING BRIX OTHERS _ _ _ _ flexible concentration Advanced options with optional software package ADVANCED DIAGNOSIS MASS FLOW DEVIATION DENSITY DEVIATION REFERENCE DENSITY DEVIATION TEMPERATURE DEVIATION TUBE DAMPING DEVIATION ELECTRODYNAMIC SENSOR DEVIATION OPERATING FREQUENCY FLUCTUATION DEVIATION TUBE DAMPIN...

Страница 52: ...ending on this setting and the engineering unit In such instances an arrow appears on the display between the measuring value and the engineering unit e g 1 2 o kg h indicating that the measuring system is computing with more decimal places than can be shown on the display DISPLAY MODE 2603 Note This function is not available unless one of the following was selected in the ASSIGN function 2600 MAS...

Страница 53: ...s not available in the information line ASSIGN 2620 Use this function to define the second reading to be displayed in the information line alternately every 10 seconds with the value defined in the function ASSIGN 2600 Options OFF MASS FLOW MASS FLOW IN VOLUME FLOW VOLUME FLOW IN CORRECTED VOLUME FLOW CORRECTED VOLUME FLOW IN DENSITY REFERENCE DENSITY TEMPERATURE MASS FLOW BARGRAPH IN VOLUME FLOW ...

Страница 54: ...ssage is generated The message in question appears on the display Fault message identified by a lightning icon If ON was selected in the ACKNOWLEDGE FAULTS 8004 function multiplex mode is continued as soon as the fault has been acknowledged and is no longer active If OFF was selected in the ACKNOWLEDGE FAULTS 8004 function multiplex mode is continued as soon as the fault is no longer active Notice...

Страница 55: ...d depending on this setting and the engineering unit In such instances an arrow appears on the display between the measuring value and the engineering unit e g 1 2 o kg h indicating that the measuring system is computing with more decimal places than can be shown on the display DISPLAY MODE 2623 Note This function is not available unless one of the following was selected in the ASSIGN function 262...

Страница 56: ... TOTALIZER 3001 p 58 OVERFLOW 3041 p 59 UNIT TOTALIZER 3001 p 58 OVERFLOW 3041 p 59 FAILSAFE ALL TOT ASSIGN 3000 p 57 SUM 3040 p 59 ASSIGN 3000 p 57 SUM 3040 p 59 ASSIGN 3000 p 57 SUM 3040 p 59 RESET ALL TOTAL 3800 p 60 Function groups CONFIGURATION 300 p 57 OPERATION 304 p 59 CONFIGURATION 300 p 57 OPERATION 304 p 59 CONFIGURATION 300 p 57 OPERATION 304 p 59 Groups TOTALIZER 1 DAA p 57 TOTALIZER ...

Страница 57: ...he totalizers are independently configurable ASSIGN 3000 Use this function to assign a measured variable to the totalizer in question Options standard OFF MASS FLOW VOLUME FLOW CORRECTED VOLUME FLOW Advanced options with optional software package CONCENTRATION TARGET MASS TARGET VOLUME TARGET CORRECTED VOLUME CARRIER MASS CARRIER VOLUME CARRIER CORRECTED VOLUME Factory setting MASS FLOW Note The t...

Страница 58: ...US o Sm3 Scf Factory setting Nm3 TOTALIZER MODE 3002 Use this function to define how the flow components are to be totalized Options BALANCE Positive and negative flow components The positive and negative flow components are balanced In other words net flow in the flow direction is registered FORWARD only positive flow components REVERSE only negative flow components Factory setting Totalizer 1 BA...

Страница 59: ...ng in the TOTALIZER MODE function see page 58 is as follows If the setting is BALANCE the totalizer balances flow in the positive and negative directions If the setting is FORWARD the totalizer registers only flow in the positive direction If the setting is REVERSE the totalizer registers only flow in the negative direction The totalizer s response to faults is defined in the FAILSAFE ALL TOTALIZE...

Страница 60: ... NO YES Factory setting NO Note If the device has a status input and if it is appropriately configured a reset for the totalizer 1 3 can also be triggered by a pulse see the ASSIGN STATUS INPUT function 5000 on page 112 FAILSAFE ALL TOTALIZERS 3801 Use this function to define the common response of all totalizers 1 3 in case of error Options STOP The totalizer is paused until the fault is rectifie...

Страница 61: ...ART VALUE FREQUENCY 4202 p 76 PULSE VALUE 4222 p 85 ON VALUE 4242 p 93 SIMULATION FREQ 4302 p 96 VALUE SIM PULSE 4323 p 98 SIMUL SWITCH POINT 4342 p 99 SWITCH ON DELAY 4702 p 103 VALUE SIM SWITCH PT 4742 p 106 CURRENT SPAN 4001 p 64 SIMULATION CURRENT 4041 p 72 ASSIGN FREQUENCY 4201 p 75 FAILSAFE VALUE 4211 p 84 ASSIGN PULSE 4221 p 85 ASSIGN STATUS 4241 p 92 ACTUAL FREQ 4301 p 96 SIMULATION PULSE ...

Страница 62: ...G BATCH UPWARDS batching progress upwards BATCH DOWNWARDS batching progress downwards Note The current range selected function CURRENT SPAN 4001 corresponds to a batching rate of 0 100 based on the batching quantity The batching software automatically sets the values for 0 4 mA and 20 mA function VALUE 0_4 mA 4002 and VALUE 20 mA 4003 Example with upward batching Value 0 4 mA 0 unit value 20 mA ba...

Страница 63: ...ATION REFERENCE DENSITY DEVIATION TEMPERATURE DEVIATION TUBE DAMPING DEVIATION ELECTRODYNAMIC SENSOR DEVIATION OPERATING FREQUENCY FLUCTUATION DEVIATION TUBE DAMPING FLUCTUATION DEVIATION Factory setting MASS FLOW Note If you select OFF the only function shown in the CONFIGURATION function group is this function in other words ASSIGN CURRENT OUTPUT 4000 Function description OUTPUTS o CURRENT OUTPU...

Страница 64: ...urrent output 1 4 20 mA NAMUR 4 20 mA HART NAMUR only current output 1 4 20 mA US 4 20 mA HART US only current output 1 0 20 mA 25 mA 4 20 mA 25 mA 4 20 mA 25 mA HART only current output 1 Factory setting 4 20 mA HART NAMUR current output 1 4 20 mA NAMUR current output 2 3 Note The option HART is only supported by the current output designated as current output 1 in the device software terminals 2...

Страница 65: ...value 0 4 to 20 mA depends on the setting in the function CURRENT SPAN q Maximum current value depends on the setting in the function CURRENT SPAN r Failsafe mode upper signal on alarm level depends on the setting in the functions CURRENT SPAN page 64 and FAILSAFE MODE page 60 A Measuring range User input 5 digit floating point number with sign Factory setting 0 kg h or 0 5 kg l or 50 C Note The a...

Страница 66: ...uring device is defined In doing so one of the two values is configured as zero flow e g 0 kg h If the effective flow drops below or exceeds the value configured as the zero flow no fault notice message is generated and the current output retains its value If the effective flow drops below or exceeds the other value a fault notice message is generated 351 354 current range and the current output r...

Страница 67: ...with sign Factory setting Depends on nominal diameter kg h or 2 kg l or 200 C Note The appropriate unit is taken from the following functions UNIT MASS FLOW 0400 UNIT VOLUME FLOW 0402 UNIT CORRECTED VOLUME FLOW 0404 UNIT DENSITY 0420 UNIT REFERENCE DENSITY 0421 UNIT TEMPERATURE 0422 see page 17 till page 21 If the option BATCH UPWARDS or BATCH DOWNWARDS only possible with the optional software pac...

Страница 68: ...d are not equal to the zero flow for example VALUE 0_4 mA 5 kg h VALUE 20 mA 10 kg h the message CURRENT OUTPUT AT FULL SCALE VALUE appears if the measuring range is exceeded or not achieved and the current output responds in accordance with the parameter settings in the function FAILSAFE MODE 4006 A0001248 SYMMETRY The current output signal is independent of the direction of flow absolute amount ...

Страница 69: ...BATCH UPWARDS or BATCH DOWNWARDS is selected in the function ASSIGN CURRENT OUTPUT 4000 the option is automatically specified and cannot be edited Detailed explanations and information How the current output responds under the following postulated conditions 1 Defined measuring range m n m and n have the same sign A0001248 and the following flow behavior A0001265 STANDARD The current output signal...

Страница 70: ...ut signal is proportional to the measured variable assigned A0001274 SYMMETRY This option is not available under these circumstances because the 0_4 mA value and the 20 mA value have different signs PULSATING FLOW Flow components outside the measuring range are buffered balanced and output after a maximum delay of 60 seconds A0001275 TIME CONSTANT 4005 Use this function to enter a time constant de...

Страница 71: ...e current output adopts the value of the lower signal on alarm level as defined in the function CURRENT SPAN 4001 see page 64 MAX CURRENT The current output adopts the value of the upper signal on alarm level as defined in the function CURRENT SPAN 4001 see page 64 HOLD VALUE not recommended Measuring value output is based on the last measuring value saved before the error occurred ACTUAL VALUE Me...

Страница 72: ...urrent output Options OFF ON Factory setting OFF Note The SIMULATION CURRENT OUTPUT message indicates that simulation is active The measuring device continues to measure while simulation is in progress i e the current measuring values are output correctly via the other outputs Caution The setting is not saved if the power supply fails VALUE SIMULATION CURRENT 4042 Note The function is not visible ...

Страница 73: ...ATION 404 INFORMATION 408 CURRENT OUTPUT 2 EAB CONFIGURATION 400 OPERATION 404 INFORMATION 408 CURRENT OUTPUT 3 EAC CONFIGURATION 400 OPERATION 404 INFORMATION 408 Function description OUTPUTS o CURRENT OUTPUT 1 o INFORMATION TERMINAL NUMBER 4080 Use this function to view the numbers of the terminals in the connection compartment and the polarity used by the current output ...

Страница 74: ...T OUTPUT 3 EAC PULSE FREQ OUTPUT 1 ECA CONFIGURATION 420 PULSE FREQ OUTPUT 2 ECB CONFIGURATION 420 Function description OUTPUTS o PULSE FREQ OUTP 1 2 o CONFIGURATION GENERAL OPERATION MODE 4200 Use this function to configure the output as a pulse frequency or status output The functions available in this function group vary depending on which option you select here Options PULSE FREQUENCY STATUS F...

Страница 75: ... TARGET MASS FLOW TARGET MASS FLOW TARGET VOLUME FLOW TARGET VOLUME FLOW CORRECTED TARGET VOLUME FLOW CARRIER MASS FLOW CARRIER MASS FLOW CARRIER VOLUME FLOW CARRIER VOLUME FLOW CORRECTED CARRIER VOLUME FLOW BLACK LIQUOR BAUME API PLATO BALLING BRIX OTHERS _ _ _ _ flexible concentration Advanced options with optional software package ADVANCED DIAGNOSIS MASS FLOW DEVIATION DENSITY DEVIATION REFEREN...

Страница 76: ...203 Note This function is not available unless the FREQUENCY setting was selected in the OPERATION MODE function 4200 Use this function to define a full scale frequency for the frequency output You define the associated measured value of the measuring range in the VALUE F HIGH function 4205 described on page 77 User input 5 digit fixed point number 2 10000 Hz Factory setting 10000 Hz Example VALUE...

Страница 77: ...unit is taken from the UNIT MASS FLOW 0400 UNIT VOLUME FLOW 0402 UNIT CORRECTED VOLUME FLOW 0404 UNIT DENSITY 0420 UNIT REFERENCE DENSITY 0421 or UNIT TEMPERATURE 0422 function see p 17 to p 21 VALUE F HIGH 4205 Note This function is not available unless the FREQUENCY setting was selected in the OPERATION MODE function 4200 Use this function to assign a variable to the end value frequency 4203 The...

Страница 78: ...uring device is defined In doing so one of the two values is configured as zero flow e g 0 kg h If the effective flow drops below or exceeds the value configured as the zero flow no fault notice message is generated and the frequency output retains its value If the effective flow drops below or exceeds the other value a fault notice message is generated 355 358 frequency area and the frequency out...

Страница 79: ...n accordance with the parameter setting in the function FAILSAFE MODE 4209 If both values defined are not equal to the zero flow for example VALUE F LOW 5 kg h VALUE F HIGH 10 kg h the message FREQUENCY OUTPUT AT FULL SCALE VALUE appears if the measuring range is exceeded or not achieved and the frequency output responds in accordance with the parameter settings in the function FAILSAFE MODE 4209 ...

Страница 80: ...fered balanced and output after a maximum delay of 60 seconds If the buffered data cannot be processed within approx 60 seconds a fault notice message appears Under certain plant conditions flow values can aggregate in the buffer for example in the case of prolonged and unwanted fluid backflow However this buffer is reset in all relevant programming adjustments which affect the frequency output Fu...

Страница 81: ...ated with a positive signal level If NEGATIVE is selected the internal transistor is activated with a negative signal level 0 V Note With the passive output configuration the output signal levels of the frequency output depend on the external circuit see examples Example for passive output circuit PASSIVE If PASSIVE is selected the frequency output is configured as an open collector A0001225 m Ope...

Страница 82: ...w In the operating status flow present the output signal level changes from a positive voltage level to 0 V A0001981 Example for output configuration PASSIVE NEGATIVE Output configuration with an external pull up resistance In the quiescent state at zero flow the output signal level at the terminals is at a positive voltage level A0004690 m Open collector n Pull Up Resistance o Transistor activati...

Страница 83: ...TIVE In the quiescent state at zero flow the output signal level at the terminals is 0 V A0004694 In the operating status flow present the output signal level changes from 0 V to a positive voltage level A0004692 The following applies for the output configuration ACTIVE NEGATIVE In the quiescent state at zero flow the output signal level at the terminals is at a positive voltage level A0004693 In ...

Страница 84: ... in the event of a fault The setting you select here affects only the frequency output It has no effect on other outputs and the display e g totalizers Options FALLBACK VALUE Output is 0 Hz FAILSAFE VALUE Output is the frequency specified in the FAILSAFE VALUE function 4211 HOLD VALUE Measured value output is based on the last measured value saved before the error occurred ACTUAL VALUE Measured va...

Страница 85: ...ASS FLOW Note If you select OFF the only function shown in the CONFIGURATION function group is this function in other words ASSIGN PULSE 4221 PULSE VALUE 4222 Note This function is not available unless the PULSE setting was selected in the OPERATION MODE function 4200 Use this function to define the flow at which a pulse is triggered These pulses can be totaled by an external totalizer and the tot...

Страница 86: ... entered the illustration applies to positive pulses P Pauses between the individual pulses Note When entering the pulse width select a value that can still be processed by an external totalizer e g mechanical totalizer PLC etc Caution If the pulse number or frequency resulting from the pulse value entered see function PULSE VALUE 4222 on page 85 and from the current flow is too large to maintain ...

Страница 87: ...th reciprocating pumps the positive and negative flow components are totaled with the signs taken into account e g 10 l and 25 l 15 l Flow components outside the maximum pulse number per second value width are buffered balanced and output after a maximum delay of 60 seconds If the buffered data cannot be processed within approx 60 seconds a fault notice message appears Under certain plant conditio...

Страница 88: ... with a positive signal level If NEGATIVE is selected the internal transistor is activated with a negative signal level 0 V Note With the passive output configuration the output signal levels of the pulse output depend on the external circuit see examples Example for passive output circuit PASSIVE If PASSIVE is selected the pulse output is configured as an open collector A0001225 m Open collector ...

Страница 89: ...low In the operating status flow present the output signal level changes from a positive voltage level to 0 V A0001981 Example for output configuration PASSIVE NEGATIVE Output configuration with an external pull up resistance In the quiescent state at zero flow the output signal level at the terminals is at a positive voltage level A0004690 m Open collector n Pull Up Resistance o Transistor activa...

Страница 90: ...TIVE In the quiescent state at zero flow the output signal level at the terminals is 0 V A0004694 In the operating status flow present the output signal level changes from 0 V to a positive voltage level A0004692 The following applies for the output configuration ACTIVE NEGATIVE In the quiescent state at zero flow the output signal level at the terminals is at a positive voltage level A0004693 In ...

Страница 91: ...to ensure that the pulse output assumes a predefined state in the event of a fault The setting you select here affects only the pulse output It has no effect on other outputs and the display e g totalizers Options FALLBACK VALUE Output is 0 pulse ACTUAL VALUE Measured value output is based on the current flow measurement The fault is ignored Factory setting FALLBACK VALUE Function description OUTP...

Страница 92: ...ANTITIES min max batching quantity PROGRESS NOTE batching end approaching Note The only options available are the monitoring functions 7240 to 7243 which have a value not equal to zero max 3 Advanced options with optional software package CONCENTRATION LIMIT TARGET MASS FLOW LIMIT TARGET MASS PROPORTION FLOW LIMIT TARGET VOLUME FLOW LIMIT TARGET VOLUME PROPORTION FLOW LIMIT TARGET CORRECTED VOLUME...

Страница 93: ...are permissible depending on the measured variable in question e g mass flow totalizer reading User input 5 digit floating point number unit Factory setting 0 kg h or 2 kg l or 200 C Note If SYMMETRY is selected in the function MEASURING MODE 4246 and values with different signs are entered for the switch on and switch off points the notice message INPUT RANGE EXCEEDED appears Only the switch on p...

Страница 94: ...t is taken from the function UNIT VOLUME FLOW 0402 or UNIT MASS FLOW 0400 If SYMMETRY is selected in the function MEASURING MODE 4246 and values with different signs are entered for the switch on and switch off points the notice message INPUT RANGE EXCEEDED appears SWITCH OFF DELAY 4245 Note This function is not available unless the STATUS setting was selected in the OPERATION MODE function 4200 U...

Страница 95: ...uctive A0001247 Note SYMMETRY cannot be selected unless the values in the ON VALUE 4242 and OFF VALUE 4244 functions have the same sign or one of the values is zero If the values have different signs SYMMETRY cannot be selected and an ASSIGNMENT NOT POSSIBLE message is displayed TIME CONSTANT 4247 Note This function is not available unless the STATUS setting was selected in the OPERATION MODE func...

Страница 96: ...was selected in the OPERATION MODE function 4200 Use this function to view the computed actual value of the output frequency Display 0 12500 Hz SIMULATION FREQUENCY 4302 Note This function is not available unless the FREQUENCY setting was selected in the OPERATION MODE function 4200 Use this function to activate simulation of the frequency output Options OFF ON Factory setting OFF Note The SIMULAT...

Страница 97: ... 4302 is active ON Use this function to define a free selectable frequency value e g 500 Hz which should be output at the frequency output with maximum pulse frequency or shortened minimum pulse width This value is used to test downstream devices and the measuring device itself User input 0 12500 Hz Factory setting 0 Hz Caution The setting is not saved if the power supply fails Function descriptio...

Страница 98: ...tive The on off ratio is 1 1 for both types of simulation The measuring device continues to measure while simulation is in progress i e the current measured values are output correctly via the other outputs Caution The setting is not saved if the power supply fails VALUE SIMULATION PULSE 4323 Note This function is not available unless the COUNTDOWN option was selected in the SIMULATION PULSE funct...

Страница 99: ...ns OFF ON Factory setting OFF Note The SIMULATION STATUS OUTPUT message indicates that simulation is active The measuring device continues to measure while simulation is in progress i e the current measured values are output correctly via the other outputs Caution The setting is not saved if the power supply fails VALUE SIMULATION SWITCH POINT 4343 Note This function is not available unless STATUS...

Страница 100: ...T OUTPUT 3 EAC PULSE FREQ OUTPUT 1 ECA CONFIGURATION 420 OPERATION 430 INFORMATION 438 PULSE FREQ OUTPUT 2 ECB CONFIGURATION 420 OPERATION 430 INFORMATION 438 Function description OUTPUTS o PULSE FREQ OUTP 1 2 o INFORMATION TERMINAL NUMBER 4380 Use this function to view the numbers of the terminals in the connection compartment and the polarity used by the pulse frequency output ...

Страница 101: ...FAULT MESSAGE NOTICE MESSAGE FAULT MESSAGE or NOTICE MESSAGE EPD Empty pipe detection only if active FLOW DIRECTION LIMIT MASS FLOW LIMIT VOLUME FLOW LIMIT CORRECTED VOLUME FLOW LIMIT DENSITY LIMIT REFERENCE DENSITY LIMIT TEMPERATURE LIMIT TOTALIZER 1 3 Advanced options with optional software package BATCHING BATCH VALVE 1 e g to control valve 1 BATCH VALVE 2 e g to control valve 2 BATCH RUNNING B...

Страница 102: ...st one relay output as a fault output and define the outputs failsafe mode The relay output is configured as a normally open NO or make contact by default It can be reconfigured as a normally closed NC or break contact by means of a jumper on the relay module see Operating Instructions Proline Promass 83 BA 059D 06 en If you select OFF or ON the only function shown in the CONFIGURATION function gr...

Страница 103: ...itive or negative values are permissible depending on the measured variable in question e g mass flow totalizer reading User input 5 digit floating point number unit Factory setting 0 kg h or 2 kg l or 200 C Note The appropriate unit is taken from the function UNIT VOLUME FLOW 0402 or UNIT MASS FLOW 0400 If SYMMETRY is selected in the function MEASURING MODE 4705 and values with different signs ar...

Страница 104: ...lay de energized A0001247 Note SYMMETRY cannot be selected unless the values in the ON VALUE 4701 and OFF VALUE 4703 functions have the same sign or one of the values is zero If the values have different signs SYMMETRY cannot be selected and an ASSIGNMENT NOT POSSIBLE message is displayed TIME CONSTANT 4706 Use this function to enter a time constant defining how the measuring signal reacts to seve...

Страница 105: ...ly open NO or make or normally closed NC or break contact see Operating Instruction Proline Promass 83 BA 059D 06 en Display MAKE CONTACT OPEN MAKE CONTACT CLOSED BREAK CONTACT OPEN BREAK CONTACT CLOSED SIMULATION SWITCH POINT 4741 Use this function to activate simulation of the relay output Options OFF ON Factory setting OFF Note The SIMULATION RELAY message indicates that simulation is active Th...

Страница 106: ...ion This value is used to test downstream devices and the measuring device itself Depending on the relay configuration as make or break contact the following selections are available Options Relay output configured as normally open make contact MAKE CONTACT OPEN MAKE CONTACT CLOSED Relay output configured as normally closed break contact BREAK CONTACT OPEN BREAK CONTACT CLOSED Caution The setting ...

Страница 107: ...AC PULSE FREQ OUTPUT 1 ECA PULSE FREQ OUTPUT 2 ECB RELAY OUTPUT 1 EGA CONFIGURATION 470 OPERATION 474 INFORMATION 478 RELAY OUTPUT 2 EGB CONFIGURATION 470 OPERATION 474 INFORMATION 478 Function description OUTPUTS o RELAY OUTPUT 1 2 o INFORMATION TERMINAL NUMBER 4780 Use this function to view the numbers of the terminals in the connection compartment and the polarity used by the relay output ...

Страница 108: ...e relay drops out at 1 m3 h and pulls up at 1 m3 h Set the switch point to 0 if your process calls for direct switchover no switching hysteresis If low flow cut off is used it is advisable to set hysteresis to a value higher than or equal to the low flow cut off rate Switch on switch off point A0001236 a Relay energized b Relay de energized Relay output configured for limit value The relay output ...

Страница 109: ...m or process error Fault oFailsafe mode outputs Inputs and totalizers A0001291 de energized A0001240 A0001238 Notice message System OK A0001052 energized A0001239 A0001237 System or process error Fault o Continuation of measuring A0001291 de energized A0001240 A0001238 Fault message or Notice message System OK A0001052 energized A0001239 A0001237 System or process error Fault o Failsafe mode or No...

Страница 110: ...ce density Temperature Totalizer Limit value not overshot or undershot A0001243 energized A0001239 A0001237 Limit value overshot or undershot A0001244 de energized A0001240 A0001238 Terminal numbers in accordance with the function TERMINAL NUMBER 4780 on page 107 Note If the measuring device has two relays the factory setting is Relay 1 o normally open contact NO Relay 2 o normally closed contact ...

Страница 111: ...5001 p 112 SIM STATUS IN 5041 p 113 CURRENT SPAN 5201 p 115 SIM CURRENT INPUT 5241 p 117 ASSIGN STATUS INPUT 5000 p 112 ACT STATUS IN 5040 p 113 TERMINAL NUMBER 5080 p 114 ASSIGN CURRENT INPUT 5200 p 115 ACTUAL VALUE CURRENT INPUT 5240 p 117 TERMINAL NUMBER 5280 p 118 Function groups CONFIGURATION 500 p 112 OPERATION 504 p 113 INFORMATION 508 p 114 CONFIGURATION 520 p 115 OPERATION 524 p 117 INFOR...

Страница 112: ...cess the batching process is canceled immediately but totalizer 3 is not reset This allows the partial filling to be read out correctly Advanced options with optional software package ADVANCED DIAGNOSIS ACQUISITION Note This function is not available unless the SINGLE SHOT setting is selected in the ACQUISITION MODE function 7410 Factory setting OFF Caution POSITIVE ZERO RETURN is active as long a...

Страница 113: ... page 112 Options OFF ON Factory setting OFF Note The SIMULATION STATUS INPUT message indicates that simulation is active The measuring device continues to measure while simulation is in progress i e the current measured values are output correctly via the other outputs Caution The setting is not saved if the power supply fails VALUE SIMULATION STATUS INPUT 5042 Note The function is not visible un...

Страница 114: ...ion group INFORMATION INPUTS F STATUS INPUT FAA CONFIGURATION 500 OPERATION 504 INFORMATION 508 Function description INPUTS o STATUS INPUT o INFORMATION TERMINAL NUMBER 5080 Use this function to view the numbers of the terminals in the connection compartment and the polarity used by the status input ...

Страница 115: ... 25 mA 4 20 mA 25 mA Factory setting 4 20 mA NAMUR Note When switching the hardware from an active factory setting to a passive output signal select a current range of 4 20 mA See Operating Instructions Proline Promass 83 BA 059D 06 en Current range operational range measuring information 0 20 mA 0 20 5 mA 4 20 mA 4 20 5 mA 4 20 mA NAMUR 3 8 20 5 mA 4 20 mA US 3 9 20 8 mA 0 20 mA 25 mA 0 24 ma 4 2...

Страница 116: ... for the process variable concerned If the current value lies outside of the selected range see function CURRENT SPAN 5201 then the process variable is set to the error value defined here and a corresponding notice message CURRENT INPUT RANGE 363 is generated User input 5 digit floating point number Factory setting Dependent on the process variable assigned to the current input see function ASSIGN...

Страница 117: ...mulation at the current input is defined in the function VALUE SIMULATION CURRENT INPUT 5242 The measuring device remains fully operational during the simulation and the current measured values are output correctly via the other outputs and the display Caution The setting is not saved if the power supply fails VALUE SIMULATION CURRENT INPUT 5242 Note This function is only available if the function...

Страница 118: ...FORMATION INPUTS F STATUS INPUT FAA CURRENT INPUT FCA CONFIGURATION 520 OPERATION 524 INFORMATION 528 Function description INPUTS o CURRENT INPUT o INFORMATION TERMINAL NUMBER 5280 This function is used to display the polarity and numbers of the terminals in the terminal compartment occupied by the current input ...

Страница 119: ... 136 DENSITY COEFF C 2 6852 p 137 MIN CARRIER TEMP 6862 p 138 TAG DESCRIPTION 6001 p 120 DEVICE ID 6041 p 121 ON VALUE LF CUT OFF 6402 p 122 EPD VALUE LOW 6423 p 125 FIXED REF DENSITY 6461 p 127 DENSITY ADJUST MODE 6482 p 130 PRESSURE 6501 p 132 DENSITY DAMPING 6602 p 133 ZEROPOINT 6803 p 135 TEMPERATURE COEFF KM 2 6841 p 136 DENSITY COEFF C 1 6851 p 137 MAX FLUID TEMP 6861 p 138 TAG NAME 6000 p 1...

Страница 120: ... 16 character text permissible A Z 0 9 punctuation marks Factory setting _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ No text BUS ADDRESS 6002 Use this function to define the address for the exchange of data with the HART protocol User input 0 15 Factory setting 0 Note Addresses 1 15 a constant 4 mA current is applied HART PROTOCOL 6003 Use this function to display if the HART protocol is active Display OFF HA...

Страница 121: ...ion BASIC FUNCTION o HART o OPERATION MANUFACTURER ID 6040 Use this function to view the manufacturer ID in decimal numerical format Display Endress Hauser 17 11 hex for Endress Hauser DEVICE ID 6041 Use this function to view the device ID in hexadecimal numerical format Display 51 81 dez for Promass 83 DEVICE REVISION 6042 Displays the device specific revision of the HART command interface Displa...

Страница 122: ... the switch on point for low flow cut off Low flow cut off is active if the value entered is not equal to 0 The sign of the flow value is highlighted on the display to indicate that low flow cut off is active User input 5 digit floating point number unit Factory setting Depends on nominal diameter Note The appropriate unit is taken from the function group SYSTEM UNITS see page 17 OFF VALUE LOW FLO...

Страница 123: ... graphic While pressure shock suppression is active the following conditions apply Current outputs o outputs the current corresponding to zero flow Pulse Freq output o outputs the frequency corresponding to zero flow Flow reading on display o0 Totalizer reading o the totalizers are pegged at the last correct value Deactivation of the pressure shock suppression The pressure shock suppression is dea...

Страница 124: ...ck BASIC FUNCTION Device Functions Proline Promass 83 PRESSURE SHOCK SUPPRESSION 6404 continued User input max 4 digit number incl unit 0 00 100 0 s Factory setting 0 00 s Function description BASIC FUNCTION o PROCESS PARAMETER o CONFIGURATION ...

Страница 125: ... ones are detected For gas measurement we strongly recommend to switch off empty pipe detection EPD VALUE LOW 6423 Note This function is not available unless the ON selection was selected in the EMPTY PIPE DETECTION function Use this function to set a lower threshold for the measured density value in order to detect possible problems in the process indicated by too low density User input 5 digit f...

Страница 126: ... the measuring pipes increases If the exciting current set in this function is exceeded error message 700 is output similar to the functions EPD VALUE LOW 6423 and EPD VALUE HIGH 6423 User input 5 digit floating point number Factory setting 100 mA deactivated Note The function is not activated until a value under 100 mA is input Entering the value 100 mA deactivates the function Function descripti...

Страница 127: ... CALCULATION function 6460 In this function a fixed value for the reference density can be entered with which the corrected volume flow or corrected volume is calculated User input 5 digit floating point number Factory setting 1 kg Nl EXPANSION COEFFICIENT 6462 Note This function is not available unless the CALCULATED REFERENCE DENSITY setting was selected in the CORRECTED VOLUME CALCULATION funct...

Страница 128: ...reference density User input 5 digit floating point number Factory setting 20 000 C The reference density is calculated as follows UN U 1 D t E t2 where t t tN UN Reference density U currently measured fluid density measuring value Promass t Actual measured temperature of fluid measuring value Promass tN Reference temperature for calculating the reference density e g 20 C D Volumetric expansion co...

Страница 129: ...system is adopted by the function ZEROPOINT see page 135 Options CANCEL START Factory setting CANCEL Caution Before carrying this out please refer to the Operating Instructions Proline Promass 83 BA 059D 06 en for a detailed description of the procedure for zero point adjustment Note Programming is locked during zero point adjustment The message ZERO ADJUST RUNNING appears on the display If the ze...

Страница 130: ...EM UNITS see page 17 MEASURE FLUID 1 6484 In this function the actual density of the first fluid is measured for density adjustment Options CANCEL START DENSITY SETPOINT 2 6485 Use this function to enter the density setpoint value for the second fluid for which you want to carry out field density adjustment User input 5 digit floating point number incl units Note The preset density entered here sh...

Страница 131: ...e outside the measuring points set at the factory or reference conditions under which the flowmeter has been calibrated The plant is used solely for measuring a fluid whose density is to be determined very accurately under constant conditions 2 point density adjustment with two fluids This type of adjustment must always be carried out when the measuring tubes are changed mechanically e g due to De...

Страница 132: ...see also Operating Instructions Proline Promass 83 BA 059D 06 en Accuracy Chapter Options OFF MEASURED This selection is only available if a current input has been selected in the function ASSIGN CURRENT INPUT 5200 PRESSURE The actual measured process pressure is read in for pressure correction via the current input FIX A fixed process pressure for pressure correction is specified see function PRE...

Страница 133: ...s in the density of the fluid e g with inhomogeneous liquids The damping acts on all functions and outputs of the measuring device User input max 5 digit number including unit 0 00 100 00 s Factory setting 0 00 s FLOW DAMPING 6603 Setting the filter depth of the digital filter The sensitivity of the flow measurement signal can be reduced with respect to interference peaks e g in the event of a hig...

Страница 134: ...ween internal and external via the current input temperature measurement Note This cell is only available if a current input is present Options INTERNAL EXTERNAL This option is only available if TEMPERATURE was selected in the function ASSIGN CURRENT INPUT 5200 Factory setting INTERNAL Function description BASIC FUNCTION o SYSTEM PARAMETER o CONFIGURATION ...

Страница 135: ...ire measuring facility in general and the accuracy of the measuring system in particular For this reason the functions described below cannot be changed even when you enter your personal code Contact the E H service organization if you have any questions about these functions Note The individual values of the functions are also provided on the sensor nameplate K FACTOR 6800 This function shows the...

Страница 136: ... sensor s parameter settings are saved on the S DAT memory chip Contact the E H service organization if you have any questions about these functions TEMPERATURE COEFFICIENT KM 6840 This function shows the temperature coefficient KM TEMPERATURE COEFFICIENT KM 2 6841 This function shows the temperature coefficient KM 2 TEMPERATURE COEFFICIENT KT 6842 This function shows the temperature coefficient K...

Страница 137: ... alter the calibration value of this coefficient DENSITY COEFFICIENT C 1 6851 This function shows the actual density coefficient C 1 Caution A density adjustment can alter the calibration value of this coefficient DENSITY COEFFICIENT C 2 6852 This function shows the actual density coefficient C 2 Caution A density adjustment can alter the calibration value of this coefficient DENSITY COEFFICIENT C...

Страница 138: ...functions are used for displaying device parameters only and consequently cannot be accessed Contact the E H service organization if you have any questions about these functions MINIMUM FLUID TEMPERATURE 6860 The lowest fluid temperature measured appears on the display MAXIMUM FLUID TEMPERATURE 6861 The highest fluid temperature measured appears on the display MINIMUM TEMP CARRIER TUBE 6862 Note T...

Страница 139: ...72 EXP COEF LIN CARR FL 7002 p 141 CONCENTRATIO N NAME 7031 p 145 ASSIGN BATCH VARIABLE 7202 p 148 OPEN VALVE 2 7222 p 154 MAX BATCHING QUANTITY 7242 p 160 BATCH DOWNWARDS 7262 p 163 VALVE 1 CLOSING TIME 7282 p 164 WARNING MODE 7403 p 166 ACQUISITION DO 7412 p 167 MINIMUM VALUE 7422 p 168 MINIMUM VALUE 7432 p 169 MINIMUM VALUE 7442 p 170 MINIMUM VALUE 7452 p 171 MINIMUM VALUE 7462 p 172 REF DENSIT...

Страница 140: ... FREQ FLUCT HISTORY 7484 p 175 TUBE DAMP FLUCT HISTORY 7494 p 177 MAXIMUM VALUE 7473 p 173 MAXIMUM VALUE 7483 p 175 MAXIMUM VALUE 7493 p 177 MINIMUM VALUE 7472 p 173 MINIMUM VALUE 7482 p 175 MINIMUM VALUE 7492 p 177 ELECTR DYN SENSORS 7471 p 173 OPERATING FREQUENCY FLUCT 7481 p 175 TUBE DAMPING FLUCT 7491 p 177 REF VALUE EL DYN SENS 7470 p 173 REF VALUE OP FREQ FLUCT 7480 p 175 REF VALUE TUBE DAMP...

Страница 141: ... function to enter the reference density density at reference temp of the carrier fluid This value is required for temperature compensated calculation of the target fluid content in a two phase fluid User input 5 digit floating point number incl units Factory setting 1 0000 kg l Note Carrier fluid transporting liquid e g water Target fluid material transported e g lime powder The appropriate unit ...

Страница 142: ...ce density density at reference temperature of the carrier fluid This value is required for temperature compensated calculation of the target fluid content in a two phase fluid User input 5 digit floating point number incl units Factory setting 1 0000 kg l Note Carrier fluid transporting liquid e g water Target fluid material transported e g lime powder The appropriate unit is taken from the funct...

Страница 143: ...e of the following was selected in the DENSITY FUNCTION function 7000 BAUME 1 SG BAUME 1 SG API PLATO BALLING BRIX Use this function to enter the fluid specific linear expansion coefficient for linear temperature curves to calculate the temperature compensated density functions User input 5 digit floating point number including unit and sign Factory setting 0 5000 e 3 1 K SQR EXPANSION COEFFICIENT...

Страница 144: ...e formula Currently measured density Currently measured temperature The concentration is calculated from the density and temperature as follows K A0 A1 U A2 U2 A3 U3 A4 U4 B1 T B2 T2 B3 T3 K Concentration U currently measured density A0 Value from function COEFFICIENT A0 7032 A1 Value from function COEFFICIENT A1 7033 A2 Value from function COEFFICIENT A2 7034 A3 Value from function COEFFICIENT A3...

Страница 145: ... concentration specification and the subsequent relevant settings up to 4 different concentrations can be preconfigured and selected when needed All settings in the subsequent functions of this function group are each only valid for the concentration specification selected in the function CONCENTRATION SELECTOR 7022 In other words the entry or option is assigned to the concentration specification ...

Страница 146: ...ion MASS 3D VOLUME 3D or OTHERS 3D was selected in the function MODE 7021 Coefficient B1 entry User input 5 digit floating point number Factory setting 0 COEFFICIENT B2 7038 Note This function does only appear if the option MASS 3D VOLUME 3D or OTHERS 3D was selected in the function MODE 7021 Coefficient B2 entry User input 5 digit floating point number Factory setting 0 COEFFICIENT B3 7039 Note T...

Страница 147: ...e which was defined for batching specification 6 in the function BATCH NAME 7201 Factory setting BATCH 1 Note By selecting a batching specification and its related settings explained below up to 6 different batchings can be preconfigured and selected as necessary All the following functions in this function group as well as the functions in the function groups VALVE PARAMETER 722 and SUPERVISION 7...

Страница 148: ... continue and the plus key stop batching name quantity in the information line by means of the batching menu assignment In this way a direct batching control station is made available locally at the measuring device by means of the user interface and the controls Select OFF if the BATCHING functionality is no longer to be used All settings related to the function e g switching contact assigned to ...

Страница 149: ...CK SUPPRESSION 6404 on page 123 Detailed explanations and information When batching using the optional software package BATCHING process related variable after run quantities or incorrect quantities can be determined and balanced out by computer by means of various functions This ensures a high level of accuracy throughout the entire batching range Response when OFF is selected The batching ends a...

Страница 150: ... low flow cut off This means that the lower the setting is for the low flow cut off the longer the after run quantity is recorded The batching is very accurate Example diagram of a batching sequence and the respective response in MODE 1 and MODE 2 A0004711 Q Flow t Time t1 time period shorter than or equal to the maximum batching time A Coarse batching quantity B Fine batching quantity C After run...

Страница 151: ...MODE 7206 SELECTION Function AVERAGING DRIP 7207 5 From five after run quantities recorded the largest and smallest are not used From the remaining three after run quantities an average after run quantity is calculated which is taken into account at the next batching AVERAGING DRIP 7207 Note This function is only available if MODE 1 or MODE 2 was selected in the COMPENSATION MODE function 7206 Use...

Страница 152: ...nt on the configuration of the outputs For 2 stage batching two relay outputs must be available in the measuring device The functions available in the function group VALVE PARAMETER page 153 are dependent on the number of batching stages number of valves selected in this function INPUT FORMAT 7209 Use this function to define the entry format of the quantities for the switch points of the valves Op...

Страница 153: ... BATCH QUANTITY 7203 is adjusted reduced increased the effective quantity switch point is automatically and dynamically adjusted e g taking 70 and changing the batching quantity from 10 to 20 liters the quantity switch point is adjusted from 7 liters to 14 liters Dynamic tracking for value data If you enter value input this value is absolute for batching quantities that do not change e g always 7 ...

Страница 154: ...to 14 liters In other words the existing value data is tracked as a percentage of the altered batching quantity CLOSE VALVE 2 7223 Use this function to specify the quantity value at which contact 2 closes This is used as a switch point for valve 2 to output via an assigned output The quantity value is entered as a or as an absolute value depending on the option in the function INPUT FORMAT 7209 Us...

Страница 155: ...batched a batching progress message should be generated Value input should be entered A0004670 v Flow velocity m s t Time V1 Valve 1 open V2 Valve 2 open m Start batching coarse batching valves 1 7220 and 2 7222 open n Valve 2 7223 closes coarse batching quantity achieved o Batching progress message 7243 p Valve 1 7221 closes end of batching x After run quantity The following parameter settings mu...

Страница 156: ...ng functions are automatically adjusted to suit the new batching quantity Function OPEN VALVE 1 0 kg Function OPEN VALVE 2 0 kg Function CLOSE VALVE 2 16 kg Example 2 The second example explains the parameter settings of the various functions for batching with the entry format in for the switch points of the valves The following batching is to take place 2 stage batching with a batching quantity o...

Страница 157: ...220 page 153 0 Valve 1 closes automatically when the batching quantity is achieved 15 kg display in function CLOSE VALVE 1 7221 page 153 Percentage data for when the second valve should open Function OPEN VALVE 2 7224 page 154 20 corresponds to 3 kg Percentage data for when the second valve should close Function CLOSE VALVE 2 7223 page 154 80 corresponds to 12 kg Example 2 a Batching specification...

Страница 158: ... is no automatic adjustment i e this value must be determined again and reentered see also fault message 471 in the Operating Instructions Proline Promass 83 BA 059D 06 en Troubleshooting Chapter Batching START is not possible when the fault message is active Note The function is not active if you enter 0 s factory setting This means that the batching valves are not closed by means of this functio...

Страница 159: ...8 there is no automatic adjustment i e this value must be determined again and reentered see also the fault message 472 in the Operating Instructions Proline Promass 83 BA 059D 06 en Troubleshooting Chapter Batching START is not possible when the fault message is active Note The function is not active if you enter 0 factory setting As a factory setting this function is assigned a fault message Thi...

Страница 160: ...ching function If this function is intended more for general monitoring purposes or if there is a short time lapse between two batching processes it is advisable to assign this function to a notice message see function ERROR CATEGORY on page 181 However while the notice message is active 60 seconds the next batching can be started and the notice message is acknowledged This function can be output ...

Страница 161: ...iate unit is taken depending on the process variable selected in the ASSIGN BATCH VARIABLE parameter and the unit configured in the SYSTEM UNITS function group The function is not active if you enter 0 factory setting If the batching process is aborted because the specified flow value is overshot the parameter BATCH COUNTER is not incremented New error message MAX FLOW with the error number 474 Th...

Страница 162: ... functions of the minus key START STOP and the plus key HOLD GO ON batching specification are defined locally In this way a direct batching control station is available locally at the measuring device by means of the user interface not access protected In the event of a fault during the batching process the batching is canceled STOP and the local display alternates between displaying the batching ...

Страница 163: ...ication is selected in the function BATCH SELECTOR 7200 BATCH SUM 7264 Use this function to display the effective overall total of all the batchings carried out Display max 7 digit floating point number unit Factory setting 0 unit Note E g in 2 stage batching the effective overall total is calculated from the coarse batching quantity fine batching quantity and after run quantity The total batching...

Страница 164: ...CA see page 17 DRIP QUANTITY 7281 Displays the after run calculated averaged internally The value displayed can be overwritten in this function and the after run can thus be adjusted The after run quantity is used to optimize the internal switch point of valve 1 User input 0 quantity unit Note The after run entered in this function is only used for the first batching process For the second and fol...

Страница 165: ...ast batching process A0001170 en Display max 7 digit floating point number Note Behavior when controlling batching process via function BATCH PROCEDURE STOP BATCHING TIME is not reset and stays at the current value START BATCHING TIME is reset and starts with the value 0 HOLD BATCHING TIME is not reset and stays at the current value GO ON BATCHING TIME is not reset and continues updating on the ba...

Страница 166: ...RT Factory setting CANCEL SELECT REFERENCE CONDITION 7402 Use this function to select the reference status which should be used to compare the advanced diagnosis parameters see function ACQUISITION MODE 7410 on page 167 Options FACTORY USER Factory setting FACTORY WARNING MODE 7403 Use this function to determine whether a warning should be generated when there is a deviation between the reference ...

Страница 167: ...ERIODICAL was selected in the ACQUISITION MODE function 7410 Use this function to specify the time interval after which the advanced diagnosis parameters should be taken The time interval starts with the confirmation of the input User input 0 99999 s Factory setting 3600 s Note A reference status must be defined prior to determining the diagnosis parameters see function SELECT REFERENCE CONDITION ...

Страница 168: ...Display 5 digit floating point number including unit and sign MAXIMUM VALUE 7423 The highest mass flow value since the saved values were last reset appears on the display Display 5 digit floating point number including unit and sign MASS FLOW HISTORY 7424 The last ten mass flow values since the saved values were last reset appear on the display Display 5 digit floating point number including unit ...

Страница 169: ...t appears on the display Display 5 digit floating point number incl units MAXIMUM VALUE 7433 The highest density value since the saved values were last reset appears on the display Display 5 digit floating point number incl units DENSITY HISTORY 7434 The last ten density values since the saved values were last reset appear on the display Display 5 digit floating point number incl units DENSITY DEV...

Страница 170: ...lues were last reset appears on the display Display 5 digit floating point number incl units MAXIMUM VALUE 7443 The highest reference density value since the saved values were last reset appears on the display Display 5 digit floating point number incl units REFERENCE DENSITY HISTORY 7444 The last ten reference density values since the saved values were last reset appear on the display Display 5 d...

Страница 171: ...ast reset appears on the display Display 5 digit floating point number including unit and sign MAXIMUM VALUE 7453 The highest temperature value since the saved values were last reset appears on the display Display 5 digit floating point number including unit and sign TEMPERATURE HISTORY 7454 The last ten temperature values since the saved values were last reset appear on the display Display 5 digi...

Страница 172: ... appears on the display Display 5 digit floating point number MAXIMUM VALUE 7463 The highest tube damping value since the saved values were last reset appears on the display Display 5 digit floating point number TUBE DAMPING HISTORY 7464 The last ten tube damping values since the saved values were last reset appears on the display Display 5 digit floating point number TUBE DAMPING DEVIATION 7465 T...

Страница 173: ...display Display 5 digit floating point number MINIMUM VALUE 7472 The lowest value of the electrodynamic sensors since the saved values were last reset appears on the display Display 5 digit floating point number MAXIMUM VALUE 7473 The highest value of the electrodynamic sensors since the saved values were last reset appears on the display Display 5 digit floating point number ELECTRODYNAMIC SENSOR...

Страница 174: ...ion is not available unless ON was selected in the WARNING MODE function 7403 Use this function to specify a limit value for the electrodynamic sensors A notice message is generated if the limit value is exceeded User input 0 99999 Factory setting 100 Function description SPECIAL FUNCTION o ADVANCED DIAGNOSIS o ELECTRODYNAMIC SENSORS ...

Страница 175: ...y appears on the display Display 5 digit floating point number Hz MINIMUM VALUE 7482 The lowest value of the operating frequency fluctuation since the saved values were last reset appears on the display Display 5 digit floating point number Hz MAXIMUM VALUE 7483 The highest value of the operating frequency fluctuation since the saved values were last reset appears on the display Display 5 digit fl...

Страница 176: ...ailable unless ON was selected in the WARNING MODE function 7403 Use this function to specify a limit value for the operating frequency fluctuation A notice message is generated if the limit value is exceeded User input 0 99999 Hz Factory setting 1000 Hz Function description SPECIAL FUNCTION o ADVANCED DIAGNOSIS o OPERATING FREQUENCY FLUCTUATION ...

Страница 177: ...on of the tube damping appears on the display Display 5 digit floating point number MINIMUM VALUE 7492 The lowest value of the tube damping since the saved values were last reset appears on the display Display 5 digit floating point number MAXIMUM VALUE 7493 The highest value of the tube damping fluctuation since the saved values were last reset appears on the display Display 5 digit floating poin...

Страница 178: ... is not available unless ON was selected in the WARNING MODE function 7403 Use this function to specify a limit value for the tube damping fluctuation A notice message is generated if the limit value is exceeded User input 0 99999 Factory setting 1000 Function description SPECIAL FUNCTION o ADVANCED DIAGNOSIS o TUBE DAMPING FLUCTUATION ...

Страница 179: ...5 p 186 SYSTEM OPTION 8241 p 187 SW REV NO I O MODULE 8303 p 187 SW REV SUB I O 8323 p 188 SW REV SUB I O 8343 p 188 SW REV SUB I O 8363 p 188 SW REV SUB I O 8383 p 188 ASSIGN SYS ERROR 8000 p 180 ACT SYS CONDITION 8040 p 183 DEVICE SOFTWARE 8100 p 186 SERIAL NUMBER 8200 p 185 SW REV NO AMPLIFIER 8222 p 186 STATUS F CHIP 8240 p 187 I O MODULE TYPE 8300 p 187 SUB IN OUTPUT TYP 8320 p 188 SUB IN OUT...

Страница 180: ...is function is only available if a system error has been selected in the function ASSIGN SYSTEM ERROR 8000 Use this function to define whether a system error triggers a notice message or a fault message If you select FAULT MESSAGES all outputs respond to an error in accordance with their defined error response patterns Options NOTICE MESSAGES display only FAULT MESSAGES outputs and display Note Pr...

Страница 181: ...ring device resumes normal operation when the fault is rectified The fault message appears in the local display until it is acknowledged by pressing the F button Factory setting OFF ALARM DELAY 8005 Use this function to define a time span for which the criteria for an error have to be satisfied without interruption before a fault or notice message is generated Depending on the setting and the type...

Страница 182: ... NO 1 YES Factory setting NO Caution If process variables which are only available via the F CHIP software options are assigned to the local display or the outputs these have to be reconfigured If reconfiguration does not take place the local display and the totalizer are set to the factory setting and the outputs are set to OFF PERMANENT STRORAGE 8007 This function indicates whether permanent sto...

Страница 183: ...IMULATION FAILSAFE MODE 8042 Use this function to set all inputs outputs and totalizers to their defined failsafe modes in order to check whether they respond correctly During this time the message SIMULATION FAILSAFE MODE appears on the display Options ON OFF Factory setting OFF SIMULATION MEASURAND 8043 Use this function to set all inputs outputs and totalizers to their defined flow response mod...

Страница 184: ... not saved if the power supply fails The appropriate unit is taken from the function group SYSTEM UNITS ACA see page 17 SYSTEM RESET 8046 Use this function to perform a reset of the measuring system Options NO RESTART SYSTEM restart without interrupting power supply Factory setting NO OPERATION HOURS 8048 The hours of operation of the device appear on the display Display Depends on the number of h...

Страница 185: ...E DEVICE SOFTWARE 8100 Displays the current device software version SUPERVISION J SYSTEM JAA VERSION INFO JCA DEVICE 810 SENSOR 820 Function description SUPERVISION o VERSION INFO o SENSOR SERIAL NUMBER 8200 Use this function to view the serial number of the sensor SENSOR TYPE 8201 Use this function to view the sensor type e g Promass F SOFTWARE REVISION NUMBER S DAT 8205 Use this function to view...

Страница 186: ...sion number of the amplifier SOFTWARE REVISION NUMBER T DAT 8225 Use this function to view the software revision number of the software used to create the content of the T DAT LANGUAGE GROUP 8226 Use this function to view the language group The following language groups can be ordered WEST EU USA EAST EU SCAND ASIA CHINA Display available language group Note The language options of the available l...

Страница 187: ...n F CHIP The software options available in the measuring device appear on the display SOFTWARE REVISION NUMBER F CHIP 8244 Note The F CHIP must be available in order to access this function Use this function to view the software revision number of the F CHIP 11 2 5 Function group I O MODULE SUPERVISION J SYSTEM JAA VERSION INFO JCA DEVICE 810 SENSOR 820 AMPLIFIER 822 F CHIP 824 I O MODULE 830 Func...

Страница 188: ...ODULE 830 I O SUBMODULE 1 832 I O SUBMODULE 2 834 I O SUBMODULE 3 836 I O SUBMODULE 4 838 Function description SUPERVISION o VERSION INFO o I O SUBMODULE 1 4 SUB IN OUTPUT TYP 1 8320 2 8340 3 8360 4 8380 Use this function to view the configuration complete with terminal numbers SOFTWARE REVISION NUMBER SUB I O TYPE 1 8323 2 8343 3 8363 4 8383 Use this function to view the software revision umber o...

Страница 189: ...0 kg h 36000 kg h 10 000 kg h 80 720 00 kg h 36000 kg h 10 000 kg p 100 1200 00 kg h 60000 kg h 10 000 kg p 150 2600 00 kg h 130000 kg h 100 000 kg p 250 7200 00 kg h 360000 kg h 100 000 kg p DN 15 25 40 50 FB Full bore versions of Promass I Nom diameter Low flow cut off Full scale value Pulse value mm approx v 0 01 m s approx v 2 m s approx 2 pulse s at 2 m s 1 0 02 kg h 4 kg h 0 001 kg p 2 0 10 ...

Страница 190: ...h Finland Suomi France Francais Netherlands Nederlands Hong Kong English India English Indonesia Bahasa Indonesia Instruments International English Italy Italiano Japan Japanese Malaysia English Norway Norsk Poland Polish Portugal Portuguese Austria Deutsch Russia Russian Sweden Svenska Switzerland Deutsch Singapore English Spain Espanol South Africa English Thailand English Czech Republic Czech H...

Страница 191: ... min 1300 00 lb min 20 000 lb p 100 44 000 lb min 2200 00 lb min 20 000 lb p 150 95 000 lb min 4800 00 lb min 200 000 lb p 250 260 000 lb min 13000 00 lb min 200 000 lb p DN 15 25 40 50 FB Full bore versions of Promass I Nominal diameter Low flow cut off Full scale value Pulse value mm approx v 0 01 m s approx v 2 m s approx 2 pulse s at 2 m s 1 0 001 lb min 0 15 lb min 0 002 lb p 2 0 004 lb min 0...

Страница 192: ...Issue Rev 0 2 12 12 Page 192 MN0M023 12 Factory settings Device Functions Proline Promass 83 This Page Intentionally Left Blank ...

Страница 193: ...CKING 38 204 OPERATION 39 220 CONFIGURATION 40 222 MULTIPLEX 42 240 CONFIGURATION 44 242 MULTIPLEX 47 260 CONFIGURATION 50 262 MULTIPLEX 53 300 CONFIGURATION 57 304 OPERATION 59 400 CONFIGURATION 62 404 OPERATION 72 408 INFORMATION 73 420 CONFIGURATION 74 430 OPERATION 96 438 INFORMATION 100 470 CONFIGURATION 101 474 OPERATION 105 478 INFORMATION 107 500 CONFIGURATION 112 504 OPERATION 113 508 INF...

Страница 194: ...ON 24 1 1002 QUICK SETUP COMMISSIONING 25 1003 QUICK SETUP PULSATING FLOW 25 1004 QUICK SETUP GAS MEASUREMENT 25 1005 QUICK SETUP BATCHING DOSING 26 1009 T DAT SAVE LOAD 26 2 2000 LANGUAGE 36 2002 DISPLAY DAMPING 36 2003 CONTRAST LCD 37 2004 BACKLIGHT 37 2020 ACCESS CODE 38 2021 DEFINE PRIVATE CODE 38 2022 STATUS ACCESS 38 2023 ACCESS CODE 38 2040 TEST DISPLAY 39 2200 ASSIGN 40 2201 100 VALUE 41 2...

Страница 195: ...RITE PROTECTION 120 6040 MANUFACTURER ID 121 6041 DEVICE ID 121 6042 DEVICE REVISION 121 6400 ASSIGN LOW FLOW CUT OFF 122 6402 ON VALUE LOW FLOW CUT OFF 122 6403 OFF VALUE LOW FLOW CUT OFF 122 6404 PRESSURE SHOCK SUPPRESSION 123 6420 EMPTY PIPE DETECTION 125 6423 EPD VALUE LOW 125 6424 EPD VALUE HIGH 125 6425 EPD RESPONSE TIME 125 6460 CORRECTED VOLUME CALCULATION 127 6461 FIXED REFERENCE DENSITY ...

Страница 196: ...VALUE DENSITY 169 7433 MAXIMUM VALUE DENSITY 169 7434 DENSITY HISTORY 169 7435 DENSITY DEVIATION 169 7436 WARNING LEVEL DENSITY 169 7440 REFERENCE VALUE REFERENCE DENSITY 170 7441 REFERENCE DENSITY 170 7442 MINIMUM VALUE REFERENCE DENSITY 170 7443 MAXIMUM VALUE REFERENCE DENSITY 170 7444 REFERENCE DENSITY HISTORY 170 7445 REFERENCE DENSITY DEVIATION 170 7446 WARNING LEVEL REFERENCE DENSITY 170 745...

Страница 197: ...86 8200 SERIAL NUMBER 185 8201 SENSOR TYPE 185 8205 SW REV NO S DAT 185 8222 SW REV NO AMPLIFIER 186 8225 SOFTWARE REV NO T DAT 186 8226 LANGUAGE GROUP 186 8240 STATUS F CHIP 187 8241 SYSTEM OPTION 187 8244 SW REV NO F CHIP 187 8300 I O MODULE TYPE 187 8303 SW REV NO I O MODULE 187 8320 SUB I O TYPE 188 8323 SW REV SUB I O 188 8340 SUB I O TYPE 188 8343 SW REV SUB I O 188 8360 SUB I O TYPE 188 836...

Страница 198: ...Issue Rev 0 2 12 12 Page 198 MN0M023 Index function matrix Device Functions Proline Promass 83 This Page Intentionally Left Blank ...

Страница 199: ...sign Additional line 44 Additional line Multiplex 47 Current input 115 Current output 62 Frequency Pulse Freq output 75 Information line 50 Information line Multiplex 53 Low flow cut off 122 Main line 40 Main line Multiplex 42 Process error 180 Pulse 85 Relay relay output 101 Status input 112 Status Pulse Freq output 92 93 System error 180 Totalizer 57 Assign Batch variable 148 Averaging drip 151 ...

Страница 200: ...Issue Rev 0 2 12 12 Page 200 MN0M023 ...

Страница 201: ...ent 138 Additional configuration 20 Additional values 13 Adjustment 129 Amplifier 186 Arbitrary unit 22 Basic Configuration user interface 36 Configuration Additional line 44 Advanced diagnostics 166 Batching function 147 Current input 115 Current output 62 Density functions 141 HART 120 Information line 50 Main line 40 Process parameter 122 Pulse Freq output 74 Relay output 101 Sensor data 135 St...

Страница 202: ...Issue Rev 0 2 12 12 Page 202 MN0M023 ...

Страница 203: ...ours 184 Other unit of concentration 16 Output signal Frequency output 81 Pulse output 88 89 90 Outputs 61 Overflow Totalizer 59 P Positive zero return 133 Pressure 12 132 Pressure correction 132 Pressure Mode 132 Pressure Shock suppression 123 124 Previous system condition 183 Process parameter Adjustment 129 Configuration 122 EPD parameter 125 Pressure correction 132 Reference parameter 127 Prog...

Страница 204: ...Issue Rev 0 2 12 12 Page 204 MN0M023 ...

Страница 205: ...Current current input 117 Current current output 72 Frequency 97 Measured variable 184 Status input 113 Switch point pulse freq output 99 Switch point Relay output 106 Value Simulation Pulse 98 Value 0_4 mA Current input 115 Current output 65 Value 20 mA Current input 116 Current output 67 Valve parameter Batching function 153 Valve 1 Closing time 164 Valve 1 Internal switch point 164 Version Info...

Страница 206: ... most current contact information visit our website at www fmctechnologies com measurementsolutions and click on the Contact Us link in the left hand column Headquarters 500 North Sam Houston Parkway West Suite 100 Houston TX 77067 USA Phone 1 281 260 2190 Fax 1 281 260 2191 Measurement Products and Equipment Erie PA USA 1 814 898 5000 Ellerbek Germany 49 4101 3040 Barcelona Spain 34 93 201 0989 B...

Отзывы: