9 Block BASIC FUNCTION
Device Functions Proline Promass 83
9.2
Group PROCESS PARAMETER
9.2.1
Function group CONFIGURATION
BASIC FUNCTION
G
HART
GAA
PROCESS PARAMETER
GIA
CONFIGURATION
640
Function description
BASIC FUNCTION
o
PROCESS PARAMETER
o
CONFIGURATION
ASSIGN LOW FLOW CUT
OFF
(6400)
Use this function to assign the switch point for low flow cut off rate suppression.
Options:
OFF
MASS FLOW
VOLUME FLOW
CORRECTED VOLUME FLOW
Factory setting:
MASS FLOW
ON-VALUE LOW FLOW
CUT OFF
(6402)
Use this function to assign a value to the switch-on point for low flow cut off.
Low flow cut off is active if the value entered is not equal to 0. The sign of the flow value
is highlighted on the display to indicate that low flow cut off is active.
User input:
5-digit floating-point number, [unit]
Factory setting:
Depends on nominal diameter
!
Note!
The appropriate unit is taken from the function group SYSTEM UNITS (see page 17).
OFF-VALUE LOW FLOW
CUT OFF
(6403)
Enter the off-value (
b
) of the low flow cut off.
Enter the switch-off point as a positive hysteresis (H) from the switch-on point (
a
).
User input:
Integer 0 to 100%
Factory setting:
50%
A0003882
m
= On-value
n
= Off-value
a
Low flow cut off is switched on
b
Low flow cut off is switched off (a + a
H)
H
Hysteresis: 0 to 100%
■
Low flow cut off active
Q
Flow
t
H
Q
m
n
b
a