![FMC Technologies Proline Promass 83 E Скачать руководство пользователя страница 184](http://html.mh-extra.com/html/fmc-technologies/proline-promass-83-e/proline-promass-83-e_description-of-device-functions_2312629184.webp)
Issue/Rev. 0.2 (12/12)
Page 184
•
MN0M023
11 Block SUPERVISION
Device Functions Proline Promass 83
VALUE SIMULATION
MEASURAND
(8044)
!
Note!
The function is not visible unless the function SIMULATION MEASURAND (8043) is
active.
Use this function to define a freely selectable value (e.g. 12 m
3
/s). This is used to test the
associated functions in the device itself and downstream signal loops.
User input:
5-digit floating-point number [unit]
Factory setting:
0 [unit]
"
Caution!
• The setting is not saved if the power supply fails.
• The appropriate unit is taken from the function group SYSTEM UNITS (ACA),
(see page 17).
SYSTEM RESET
(8046)
Use this function to perform a reset of the measuring system.
Options:
NO
RESTART SYSTEM (restart without interrupting power supply)
Factory setting:
NO
OPERATION HOURS
(8048)
The hours of operation of the device appear on the display.
Display:
Depends on the number of hours of operation elapsed:
Hours of operation < 10 hours
o
display format = 0:00:00 (hr:min:sec)
Hours of operation 10...10,000 hours
o
display format = 0000:00 (hr:min)
Hours of operation > 10,000 hours
o
display format = 000000 (hr)
Function description
SUPERVISION
o
SYSTEM
o
OPERATION