Innovative High Temperature Fiber Optic Infrared Pyrometers
Device Options
61
is transferred to the PROFINET
IO controller
message active
Message process alarm
The process alarm of pyrometer
is not transferred to the
PROFINET IO controller
message inactive
is transferred to the PROFINET
IO controller
message active
Behavior on module fault
set process data to zero,
set process data to last value
8.3.4. Structure of the input/output data
8.3.4.1. Pyrometer module input data
The input data length is 23 Byte.
Address
without offset
Length
Format
Value
0
4 Byte
REAL (Big Endian, Motorola)
Target Temperature 2 color
4
4 Byte
REAL (Big Endian, Motorola)
Target Temperature 1 color wide
8
4 Byte
REAL (Big Endian, Motorola)
Target Temperature 1 color narrow
12
4 Byte
REAL (Big Endian, Motorola)
Internal temperature
16
4 Byte
DWORD
Error Code
20
1 Byte
BYTE Bit0 (Bool)
Trigger state ( 0
– reset, 1 – set)
21
2 Byte
INT(Big Endian, Motorola)
Measured attenuation
8.3.4.2. Pyrometer module output data
The output data length of Input/Output module is 5 Byte. The output data may be used to
change the initialization of the device (which was set once at start-up) when the bus is in data
exchange mode.
To do so the following structure is defined:
Address
without offset
Length
Format
Value
0
1 Byte
BYTE
Type of parameter
1
4 Byte
REAL/ WORD
(Big Endian, Motorola)
Parameter
The <Type of parameter> gives the meaning of the following parameters (with the same format
as described in the section 8.3.3.1 for Pyrometer parameters)
Parameter type
Meaning
Format
0
Do not change anything
1
Slope
REAL
2
Emissivity
REAL
3
Transmissivity
REAL
4
Averaging time
REAL
5
Peak hold time
REAL
6
Valley hold time
REAL
7
Set point for the relay
REAL
8
Laser control
WORD
If <Type of parameter> is set to 0 then the output data gets ignored.
As default, it should be set to 0 (zero).
8.3.5. Diagnostics
The diagnostics information of the fieldbus communicator can be read out acyclically using
standard diagnostics data sets defined in the PROFINET IO specification.
Содержание endurance series
Страница 4: ......
Страница 8: ...iv...
Страница 10: ...vi...
Страница 24: ...Endurance Series Users Manual 12 3 4 1 1 Measurement Spot Size Diagrams for F0 Narrow Focus Option...
Страница 25: ...Innovative High Temperature Fiber Optic Infrared Pyrometers Technical Data 13...
Страница 26: ...Endurance Series Users Manual 14 3 4 1 2 Measurement Spot Size Diagrams for F1 Close Focus Option...
Страница 27: ...Innovative High Temperature Fiber Optic Infrared Pyrometers Technical Data 15...
Страница 28: ...Endurance Series Users Manual 16 3 4 1 3 Measurement Spot Size Diagrams for F2 Infinity Focus Option...
Страница 69: ...Innovative High Temperature Fiber Optic Infrared Pyrometers Signal Processing 57 defaults are restored...