8.3.2.2. Configuration
The Endurance
®
PROFINET IO device configuration is in accordance with the physical
arrangement of the node (slot oriented).
Module slot 0 contains the Endurance
®
PROFINET in its function as station substitute. It does
not deliver process data itself, but provides the parameters required to perform communication
settings of the I/O device (e.g. update cycle time).
Slot 1 (Input/Output module) reflects the physical arrangement of the pyrometer, that deliver a
part of the process and diagnostics data. All specific information on the relevant module is
contained in the associated GSD file.
8.3.3. Parameter Setting
The parameter setting of a connected pyrometer happens
via “record data” sets. The I/O
module allows diagnostics message to be locked or released. Once all parameter settings are
performed, the I/O device signals that it is ready to send cyclic productive data.
8.3.3.1. Pyrometer parameters
Certain pyrometer characteristics are parameterizable during the configuration. The parameters
of the pyrometer substitute are used to set the overall settings of the PROFINET I/O node.
Some of the setting are used in the module as default settings and can be optionally overwritten
within the module configuration.
Parameter
Description
Setting
Temperature unit
Set the temperature unit
Celsius
Fahrenheit
Color mode
1 , 2 color
Slope
* 1000 (0.9
900)
850 … 1150
Emissivity
* 1000 (0.9
900)
100 … 1100
Transmissivity
* 1000 (1.0
1000)
100 … 1100
Sensor offset
-
200 … +200
Sensor gain
800 … 1200
Averaging time
* 0.1s (1s
10)
0 …3000
Valley hold time
* 0.1s (1s
10)
0 …3000
Peak hold time
* 0.1s (1s
10)
0 …3000
Setpoint relay
in °C /°F
dev. range min.. max
Deadband
1 …99
Decay rate
0 …9999
Relay alarm output control
normally open,
normally closed,
permanently open,
permanently closed.
Laser control
off / on / flashing/ trigger
Panel lock
locked / unlocked
Analog output mode
Set output mode
0 … 20 mA / 4 … 20 mA
Bottom temperature of output
Set bottom temperature of
analog output
0…9999°C /°F
Top temperature of output
Set top temperature of analog
output
0…9999°C /°F
8.3.3.2. Profinet alarm behavior
Parameter
Description
Setting
Message diagnostics alarm
The diagnostics information of
pyrometer is not transferred to
the PROFINET IO controller
message inactive
Содержание endurance series
Страница 4: ......
Страница 8: ...iv...
Страница 10: ...vi...
Страница 24: ...Endurance Series Users Manual 12 3 4 1 1 Measurement Spot Size Diagrams for F0 Narrow Focus Option...
Страница 25: ...Innovative High Temperature Fiber Optic Infrared Pyrometers Technical Data 13...
Страница 26: ...Endurance Series Users Manual 14 3 4 1 2 Measurement Spot Size Diagrams for F1 Close Focus Option...
Страница 27: ...Innovative High Temperature Fiber Optic Infrared Pyrometers Technical Data 15...
Страница 28: ...Endurance Series Users Manual 16 3 4 1 3 Measurement Spot Size Diagrams for F2 Infinity Focus Option...
Страница 69: ...Innovative High Temperature Fiber Optic Infrared Pyrometers Signal Processing 57 defaults are restored...