1. Installation
1−28
Festo P.BE−CPX−FB23−EN en 0308NH
1.3.5
Bus termination with terminating resistors
Please note
If the CPX terminal is at the beginning or end of the field
bus system, a bus termination is required.
·
Use a bus termination at both ends of a bus segment.
A resistor between Data A and Data B is used as a bus
termination (depending on cable type, see table).
1
Festo field bus plug
2
Connection for
continuing field bus
sealed with a
blanking plug
3
Terminating resistor
between DA and DB
4
Festo sub−base
1
2
3
4
*NC*
DB DA
DG
*NC*
DB DA
DG
*NC*
DG
DB
DA
FBS−AB−1−KL−5POL
FG
SLD
DG
Festo
DB
DA
Fig.1/7: Bus termination
Cable type
Terminating resistor
FANC 110SBH 0.5 mm
2
x 3
1)
110 , 0.5 W
CSFV 110SLAB
2)
110 , 0.5 W
1)
Kurashige Electronics, Inc.
2)
Daiden K.K.
Содержание CPX-FB23
Страница 2: ......
Страница 4: ...Contents and general instructions II Festo P BE CPX FB23 EN en 0308NH...
Страница 15: ...Installation 1 1 Festo P BE CPX FB23 EN en 0308NH Chapter 1...
Страница 45: ...Commissioning 2 1 Festo P BE CPX FB23 EN en 0308NH Chapter 2...
Страница 86: ...2 Commissioning 2 42 Festo P BE CPX FB23 EN en 0308NH...
Страница 87: ...Diagnosis and error treatment 3 1 Festo P BE CPX FB23 EN en 0308NH Chapter 3...
Страница 104: ...3 Diagnosis and error treatment 3 18 Festo P BE CPX FB23 EN en 0308NH...
Страница 105: ...Technical appendix A 1 Festo P BE CPX FB23 EN en 0308NH Appendix A...
Страница 117: ...Index B 1 Festo P BE CPX FB23 EN en 0308NH Appendix B...
Страница 118: ...B Index B 2 Festo P BE CPX FB23 EN en 0308NH Contents B Index B 1 B 1 Index B 3...