1. Installation
1−8
Festo P.BE−CPX−FB23−EN en 0308NH
1.2.2 Setting the DIL switches
There are 5 DIL switches for configuring the field bus node.
These are situated under the DIL switch cover.
1
DIL switches 1 and 2:
Operating mode
and baud rate
2
DIL switch 2:
Baud rate
3
DIL switch 3:
CC link slave
address
4
DIL switch 4:
Number of stations
per slave
5
DIL switch 5:
HOLD/CLEAR,
System diagnosis
1
2
1
2
ON
ON
1
2
3
1234
567
8
ON
1
2
1
2
ON
ON
4
5
Fig.1/3:
DIL switches in the field bus node
(further information on
1
...
5
see following pages)
Proceed as follows:
1. Switch off the power supply.
2. Remove the DIL switch cover (see section 1.2.1).
3. Set the DIL switches as described on the following pages.
4. Fit the DIL switch cover (tightening torque 0.4 Nm, see
Содержание CPX-FB23
Страница 2: ......
Страница 4: ...Contents and general instructions II Festo P BE CPX FB23 EN en 0308NH...
Страница 15: ...Installation 1 1 Festo P BE CPX FB23 EN en 0308NH Chapter 1...
Страница 45: ...Commissioning 2 1 Festo P BE CPX FB23 EN en 0308NH Chapter 2...
Страница 86: ...2 Commissioning 2 42 Festo P BE CPX FB23 EN en 0308NH...
Страница 87: ...Diagnosis and error treatment 3 1 Festo P BE CPX FB23 EN en 0308NH Chapter 3...
Страница 104: ...3 Diagnosis and error treatment 3 18 Festo P BE CPX FB23 EN en 0308NH...
Страница 105: ...Technical appendix A 1 Festo P BE CPX FB23 EN en 0308NH Appendix A...
Страница 117: ...Index B 1 Festo P BE CPX FB23 EN en 0308NH Appendix B...
Страница 118: ...B Index B 2 Festo P BE CPX FB23 EN en 0308NH Contents B Index B 1 B 1 Index B 3...