1. Installation
1−20
Festo P.BE−CPX−FB23−EN en 0308NH
Bus cable specifications after CC−Link
Use a twisted, screened 3−core cable for connecting the field
bus.
Cross−sectional area:
0.5 mm
2
(1 pair)
Line resistance:
Ţ
37.8 /km (20 °C)
Capacitance per unit length:
60 nF/km (1 kHz)
Impedance:
110 ± 15 %
Isolation resistor:
ţ
10,000 M/km
Electric strength:
500 V DC for 1 minute
Reference cable:
FANC 110SBH 0.5 mm
2
x 3 (Kurashige Electronics, Inc.)
(terminating resistor 110 , 0.5 W)
Other possibilities:
CSFV110−SLAB (Daiden K.K.)
or corresponding cable as per cable specification 1.1
(terminating resistor 110 , 0.5 W)
Please note
If cables of different types are used, normal data trans
mission cannot be guaranteed.
·
Make sure that only one type of cable is used in a field
bus string.