TST
Assembly instructions
FUZ2 -A/-B/-C/-CX/-L
FEIG ELECTRONIC GmbH
Page 57 of 71
FUZ2-A-B-C-CX-L_Montageanleitung_GB
_10.docx
No.
Description
Possible reason for error
F.752
Loss of communication with
encoder
• Interface cable defective / interrupted
• Channel A and B connected over cross
• Absolute encoder processor electronics defective
• Defective hardware or electrically noisy environment
• Use a shielded control cable
• Install a RC element (100Ω+100nF) at the brake
F.760
Position outside of window
• Position encoder drive defective
• Absolute encoder processing electronics defective
• Defective hardware or electrically noisy environment
F.763
DES-B Error
• Position encoder drive defective -> make a reset
F.766
Internal error TST PD/PE
• The position encoder TST PD / PE is disturbed -> make a reset
F.767
Overtemperature TST PD
• The temperature in the encoder housing is to high
F.768
Battery voltage
• The voltage of the buffer battery is to low → change battery
F.769
Rotation speed of PD shaft to high
• The rotation speed of the shaft where the encoder is mounted is to high → mount the encoder on another shaft
F.770
Door way is to high for the
parameter set Encoder resolution
• The Value of the Parameter P.202 (set Encoder resolution) is to high for the combination encoder and door.
F.801
Wrong Test of input 1 of the mobile
unit TST FSx
• Input 1 of the mobile unit was tested wrong
• The device which is connected to the input does not work correctly
• The mobile unit is defective
F.802
Wrong Test of input 2 of the mobile
unit TST FSx
• Input 2 of the mobile unit was tested wrong
• The device which is connected to the input does not work correctly
• The mobile unit is defective
F.803
Wrong Test of input 3 of the mobile
unit TST FSx
• Input 3 of the mobile unit was tested wrong
• The device which is connected to the input does not work correctly
• The mobile unit is defective
F.804
Wrong Test of input 4 of the mobile
unit TST FSx
• Input 4 of the mobile unit was tested wrong
• The device which is connected to the input does not work correctly
• The mobile unit is defective
F.80A
Wrong Test of input A of the
stationary unit TST FSx
• Input A of the stationary unit was tested wrong
• The device which is connected to the input does not work correct
• The stationary unit is defective