General operating instructions to set parameters
7.1 Open the parameter operation mode
1.
Turn off the door controller and wait until the display has been completely extinguished.
2.
SERVICE
Open the cover of the enclosure and switch the DIP switch S500 (see illustration) to ON. The
service mode is activated and you can close the cover.
S500
Figure 34: DIP switch position
The service mode is automatically reset after approx. 1 hour. In order to reach service mode again, the
controller must be turned off for a short period and then turned on again or a reset must be performed.
3.
Close the cover of the enclosure and turn on the controller.
4.
+
keep these pressed simultaneously to reach the parameter
selection. (either appears
1: Clear text display
or
2: 7-
Segmentdisplay
)
P: door cycles
000# 1234Zyk
P.
000
5.
or
Use the arrow keys to select the required parameter.
ATTENTION
Not all the parameters are visible or may be changed
immediately; this always depends on the password and the
type of position set.
P: Offenhalt1 |
010= 10 s
P.
010