TST
Assembly instructions
FUZ2 -A/-B/-C/-CX/-L
FEIG ELECTRONIC GmbH
Page 44 of 71
FUZ2-A-B-C-CX-L_Montageanleitung_GB
_10.docx
9.2
… with mechanical limit switches
1.
Press the
CLOSE key to move the door to a distance of approx. 50 cm from the closed position
If the door does not move, the motor lacks power. With the aid of the boost (performance
increase at low speeds) the motor can be supplied with an increase in power.
(see Chapter 9.5), if necessary, if necessary, check that the brake was released.
The distance depends to a large extent on the door type and the speed; increase this value
for fast moving doors.
If the door moves in the incorrect direction: incorrect motor rotary field, turn off controller
and reverse the 2 motor connections.
2.
Set lower pre-limit switch so that it just trips
3.
Press the
CLOSE key to move the door to a distance of approx. 10 cm from the closed position
The distance depends to a large extent on the door type and the speed; increase this value
for fast moving doors.
4.
Set lower limit switch so that it just trips
Do not travel past the limit switch at the limit positions!
5.
Press the
OPEN key to move the door to a distance of approx. 50 cm from the opened position
If the door does not move, the motor lacks power. With the aid of the boost (performance
increase at low speeds) the motor can be supplied with an increase in power.
(see Chapter 9.5), if necessary, if necessary, check that the brake was released.
The distance depends to a large extent on the door type and the speed; increase this value
for fast moving doors.
6.
Set upper pre-limit switch so that it just trips.
7.
Press
OPEN key to move the door to approx. 10 cm from the opened position.
The distance depends to a large extent on the door type and the speed; increase this value
for fast moving doors.
8.
Set upper limit switch so that it just trips
Do not travel past the limit switch at the limit positions!
9.
If required by the door type: adjust upper and lower EMERGENCY limit switches.
Connect the NC
contacts, e.g. the safety circuit, in series with thermo pill.
10.
By pressing the
STOP key and
OPEN key to enter parametrization mode and select
Parameter P.980 "Service Mode", open and set parameter value "2" to "0" (Automatic mode).
11.
Correct limit switch positions for door OPEN and door CLOSE as needed by fine adjustment of the
limit positions in automatic mode.
WARNING
To prevent the door from moving unintentionally, adjust the limit switches only when the
Emergency-STOP is activated or with the controller turned off !
12.
The door may now be operated in automatic mode.