5-10
J codes: Application Functions
Code
Incre-
ment
Unit
Change
when
running
Data
copying
Default
setting
Refer to
page:
J01
0: Disable
-
-
N
Y
0
-
1: Enable (Process control, normal operation)
2: Enable (Process control, inverse operation)
3: Enable (Dancer control)
J02
(Remote command SV)
0: UP/DOWN keys on keypad
-
-
N
Y
0
1: PID command 1
3: T erminal command
UP
/
DOWN
control
4: Command via communications link
J03
P (Gain) 0.000 to 30.000 *1
0.001
times
Y
Y
0.100
J04
I (Integral time) 0.0 to 3600.0 *1
0.1
s
Y
Y
0.0
J05
D (Differential time) 0.00 to 600.00 *1
0.01
s
Y
Y
0.00
J06
(Feedback filter) 0.0 to 900.0
0.1
s
Y
Y
0.5
J10
0 to 200
1
%
Y
Y
200
J11
(Select alarm output)
0: Absolute-value alarm
-
-
Y
Y
0
1: Absolute-value alarm (with Hold)
2: Absolute-value alarm (with Latch)
3: Absolute-value alarm (with Hold and Latch)
4: Deviation alarm
5: Deviation alarm (with Hold)
6: Deviation alarm (with Latch)
7: Deviation alarm (with Hold and Latch)
J12
(Upper level alarm (AH)) -100 to 100
1
%
Y
Y
100
J13
(Lower level alarm (AL)) -100 to 100
1
%
Y
Y
0
J18
(Upper limit of PID process output)
1
%
Y
Y
999
J19
(Lower limit of PID process output)
1
%
Y
Y
999
J56
(Speed command filter) 0.00 to 5.00
0.01
s
Y
Y
0.10
J57
(Dancer reference position) -100 to 100
1
%
Y
Y
0
J58
(Detection width of dancer
0:
1
%
Y
Y
0
position deviation) 1 to 100
J59
0.000 to 30.00 *1
0.001
times
Y
Y
0.100
J60
0.0 to 3600.0 *1
0.1
s
Y
Y
0.0
J61
0.00 to 600.00 *1
0.01
s
Y
Y
0.00
J62
(PID control block selection)
1
-
N
Y
0
J63
Overload Stop
0: T orque
-
-
Y
Y
0
5-65
(Detection value)
1: Current
J64
(Detection level) 20 to 200
0.1
%
Y
Y
100
J65
(Mode selection)
0: Disable
-
-
N
Y
0
1: Decelerate to stop
2: Coast to a stop
3: Hit mechanical stop
J66
(Operation condition)
0:
-
-
Y
Y
0
1: Enable at constant speed
2: Enable anytime
J67
(T imer)
0.01
s
Y
Y
0
J68
0 to 200
1
%
Y
Y
100
5-66
J69
(Brake OFF frequency) 0.0 to 25.0
0.1
Hz
Y
Y
1.0
J70
(Brake OFF timer) 0.0 to 5.0
0.1
s
Y
Y
1.0
J71
(Brake ON frequency) 0.0 to 25.0
0.1
Hz
Y
Y
1.0
J72
(Brake ON timer) 0.0 to 5.0
0.1
s
Y
Y
1.0
J73
Reserved *2
0.0 to 1000.0 s
0.1
s
Y
Y
0.0
-
J74
-999 to 999
1
p
Y
Y
0
J75
0 to 9999
1
p
Y
Y
0
J76
-999 to 999
1
p
Y
Y
0
J77
0 to 9999
1
p
Y
Y
0
J78
-999 to 999
1
p
Y
Y
0
J79
0 to 9999
1
p
Y
Y
0
J80
0 to 400 Hz
0.1
Hz
Y
Y
0
J81
-999 to 999
1
p
Y
Y
0
J82
0 to 9999
1
p
Y
Y
0
J83
0 to 500
1
p
Y
Y
0
J84
0.0 to 1000.0 s
0.1
s
Y
Y
0
J85
0 to 500
1
p
Y
Y
0
J86
-
-
Y
Y
0
Bit 0 : PID output pole
0 = addition, 1 = subtraction
(Brake OFF current)
D (Differential time) 2
0 : Manual mode
1 : Auto mode
0.00 to 600.00
PID Control (Mode selection)
Braking Signal
I (Integral time) 2
P (Gain) 2
PID Control (Anti reset windup)
Disable switching PID constant
Bit 1 : Select compensation of output ratio
0 = speed command, 1 = ratio
-150 to 150
999
:
Disable
-150 to 150
999
:
Disable
Enable at constant speed and during deceleration
Data setting range
Name
*
1
When you make settings from the keypad, the incremental unit is restricted by the number of digits that the LED monitor can
display.
(Example) If the setting range is from -200.00 to 200.00, the incremental unit is:
"1" for -200 to -100, "0.1" for -99.9 to -10.0 and for 100.0 to 200.0, and "0.01" for -9.99 to -0.01 and for 0.00 to 99.99.
*
2
These function codes and their data are displayed, but they are reserved for particular manufacturers. Unless otherwise
specified, do not access these function codes.