3-8
Setting up the frequency command with
and
keys under PID process control
When function code F01 is set to "0" (
/
keys on keypad) and frequency command 1 is
selected as a manual speed command (when disabling the frequency setting command via
communications link or multi-frequency command), switching the LED monitor to the speed monitor
in Running mode enables you to modify the frequency command with the
/
keys.
In Programming or Alarm mode, the
/
keys are disabled to modify the frequency command.
You need to switch to Running mode.
Table 3.5 lists the combinations of the commands and the figure illustrates how the manual speed
command
entered via the keypad is translated to the final frequency command
.
The setting procedure is the same as that for setting of a usual frequency command.
Table 3.5 Manual Speed (Frequency) Command Specified with
/
Keys and Requirements
PID control
(Mode
selection)
J01
LED
monitor
E43
Frequency
command 1
F01
Multi-
frequency
SS2
Multi-
frequency
SS1
Communi-
cations
link
operation
LE
Cancel PID
control
Hz/PID
Pressing
/
keys controls:
OFF
(PID
enabled)
PID output
(as final frequency
command)
0 OFF
OFF
OFF
ON
(PID
disabled)
Manual speed
(frequency)
command set by
keypad
OFF
(PID
enabled)
PID output
(as final frequency
command)
1 or 2
0
Other than the above
ON
(PID
disabled)
Manual speed
(frequency)
command currently
selected