2-9
2.3.3 Recommended
wire
sizes
Table 2.7 lists the recommended wire sizes. The recommended wire sizes for the main circuits are
examples of using HIV single wire (for 75
°
C) at an ambient temperature of 50
°
C.
Table 2.7 Recommended Wire Sizes
Recommended wire size (mm
2
)*
1
Main circuits
Main circuit
power input
[L1/R,L2/S,L3/T]
[L1/L,L2/N]
Power su
pply v
olt
ag
e
Nominal
applied
motor
Inverter type
w/ DCR w/o DCR
Ground-
ing
[ G]
Inverter
output
[U, V, W]
DCR
[P1,
P (+)]
Braking
resistor
[P(+),
DB]
Control
circuit
0.1 FRN0.1E1S-2
0.2 FRN0.2E1S-2
0.4 FRN0.4E1S-2
0.75 FRN0.75E1S-2
1.5 FRN1.5E1S-2
2.2 FRN2.2E1S-2
3.7 FRN3.7E1S-2
2 2 2 2
5.5 FRN5.5E1S-2
2
3.5 3.5
3.5
7.5 FRN7.5E1S-2
3.5 5.5
3.5
5.5
11 FRN11E1S-2
5.5 14
5.5
8 8
Three-ph
ase 2
00 V
15 FRN15E1S-2
14 22 8 14 14
2
0.75
to
1.25
0.4 FRN0.4E1S-4
0.75 FRN0.75E1S-4
1.5 FRN1.5E1S-4
2.2 FRN2.2E1S-4
3.7
4.0*
2
FRN3.7E1S-4
FRN4.0E1S-4E
5.5 FRN5.5E1S-4
2
7.5 FRN7.5E1S-4
2 2
11 FRN11E1S-4
2
3.5
2
3.5
Three-ph
ase 4
00 V
15 FRN15E1S-4
3.5 5.5
3.5
3.5 5.5
2
0.75
to
1.25
0.1 FRN0.1E1S-7
0.2 FRN0.2E1S-7
0.4 FRN0.4E1S-7
0.75 FRN0.75E1S-7
1.5 FRN1.5E1S-7
2
Three-ph
ase
200 V
2.2 FRN2.2E1S-7
2
3.5
2 2 2 2
0.75
to
1.25
DCR: DC reactor
*
1
Use the terminal crimp with an insulation sheath or with processing by the insulation tube.
Use the insulated wire of 75
°
C, 600 V, HIV-insulated. This selection assumes the inverter is used in
ambient temperature at 50
°
C.
*
2
The nominal applied motor rating of FRN4.0E1S-4E to be shipped to the EU is 4.0 kW.
Note:
A box (
) in the above table replaces A, C, E, J, or K depending on the shipping destination.
For three-phase 200 V class series of inverters, it replaces A, C, J, or K.