3-11
3.3.3 Running/stopping the motor
By factory default, pressing the
key starts
running the motor in the forward direction and
pressing the
key decelerates the motor to
stop. The
key is enabled only in Running
mode.
The motor rotational direction can be selected
by changing the setting of function code F02.
Operational relationship between function code F02 (Operation method) and
key
Table 3.8 lists the relationship between function code F02 settings and the
key, which determines
the motor rotational direction.
Table 3.8 Motor Rotational Direction Specified by F02
Data for F02
Pressing the
key runs the motor:
0
In the direction commanded by the
terminal [FWD] or [REV]
1
key disabled
(The motor is driven by terminal
[FWD] or [REV] command.)
2
In the forward direction
3
In the reverse direction
(Note)
The rotational direction of
IEC-compliant motors is opposite
to that of the motor shown here.
For the details on operations with function code F02, refer to Chapter 5 "FUNCTION CODES."
When the keypad is in use for specifying the frequency settings or driving the motor, do not
disconnect the keypad from the inverter when the motor is running. Doing so may stop the
inverter.
3.4 Programming
Mode
The Programming mode provides you with these functions--setting and checking function code data,
monitoring maintenance information and checking input/output (I/O) signal status. The functions can
be easily selected with the menu-driven system. Table 3.9 lists menus available in Programming
mode. The leftmost digit (numerals) of each letter string on the LED monitor indicates the
corresponding menu number and the remaining three digits indicate the menu contents.
When the inverter enters Programming mode from the second time on, the menu selected last in
Programming mode will be displayed.