Xl-4, XL-4B, and XL-5 Hookup and Installation Instructions
Version 4
3–12
Dry Contacts
Contacts rated 110 VAC, 24 VDC, 3 Amps.
Trigger Connector
The control panel contains eight voltage level triggers that are provided through connector
P3. The connections for the trigger outputs are displayed below and requires connection of
FBII part number 7103UL Trigger Connector. The triggers can be programmed for pulsed or
latched operation through the programming questions. The triggers when active deliver
12VDC, 25ma maximum.
Pin 3 of the trigger connector is an Arm/Disarm trigger which can be selected for high or low
output through the programming questions and is normally active high (high = 3mA, low =
12mA).
Trigger 7 is the data line and Trigger 8 is the clock line for the XL-4705 relay module, when
activated.
COLOR CONNECTION
White w/Yellow stripe Trigger 7
White w/Orange stripe Trigger 8
White w/Red stripe
Trigger 6
White w/Brown stripe
Arming Status
White w/Black stripe
Trigger 5
Grey
Trigger 4
Blue
Trigger 3
Yellow
Trigger 2
Orange
Ground
Red
Trigger 1
Brown
Ground
Yellow Wire
Brown Wire
TR7
TR6
TR5
TR4
TR3
TR2
TR1
TR8
ARM
GND
GND
27
29
28
SET UP AS DRY CONTACTS. NO FIRE ON SYSTEM.
NORMALLY OPEN
COMMON
NORMALLY CLOSED