Section 3 – System Wiring and Hookup
3–9
JP2
Jumper 2 is used in conjunction with the application of relay #1. JP2 should be cut if relay #1
is being used with dry contacts, or left connected if relay #1 is being used as a bell output.
Default Reset
Shorting TP1 to TP2 will cause the panel to revert to the original panel default values. This
should only be performed if the programming status is unknown and the panel defaults are
desired. The control panel default values can be viewed in the LCD Keypad Programming
Guide.
To perform a default reset, remove all power to the panel, AC & DC. Short TP1 & TP2 and
while short is still intact reapply power AC then DC. Wait 8 to 10 seconds then remove the
short while the unit is still powered. The system default reset may take 20 to 30 seconds.
If the INSTALLER LOCKOUT option has been selected within the programming sequence then a
default reset through these pins will perform a default with the exception of the CSID and Installer
Code.
Panel Reset
Shorting connection TP3 to TP2 while the system is powered on will cause a panel reset to
occur. This will not alter any of the programming information within the system.
Local Printer Connection
This pin (P1) is used to connect to the 7130 Serial Printer Interface Module to output the
System Log to a local printer.
NOTE: P1 may be labeled as GND START on the PC board.
Line Seizure
This pin (P2) is active (low) when line seizure has occurred.
Ground
Connect terminal to a cold water grounding pipe utilizing #16AWG wire at a distance no
greater than 15 feet. If the premises pipes terminate in PVC, this terminal must be
connected to a 6-foot grounding rod.
To increase lightning and static protection on this panel, we strongly recommend the use of the
Ground Lug
as instructed above instead of using terminal 18. The Ground Lug is located on the
lower left-hand corner of the panel
.
Telephone Line
Connect an FBII model 368 cord to an RJ31X jack as follows:
19 Green Telco Tip
20 Red Telco Ring
21 Brown Home Tip
22 Grey Home Ring
The FCC registration number is (AE398E-69554 AL-E) and the ringer equivalent is (0.0B).
The control panel should not be connected to party lines or coin operated phone lines. The
device should not be connected to a telephone line that has call waiting, unless the call
waiting interrupt numbers have been programmed into the panel dialing sequence.