Xl-4, XL-4B, and XL-5 Hookup and Installation Instructions
Version 4
3–2
Wiring Diagram
1
Z
1
3
Z
2
5
6
Z
4
7
Z
5
8
9
Z
6
10
Z
7
11
12
Z
8
13
14
15
16
2
4
Z
3
1W
2.
2k
1W
2.
2k
1W
2.
2k
1W
2.
2k
KEYPADS
XK-7LC/XK-716
XK-5LC/XK-516
Max 280mA
(150 mA UL)
AUX POWER
(See #34, 35)
[–]
[+]
18
19
20
21
22
23
24
25
26
27
28
29
T R
T R
N/O
N/C
COM
*N/O
N/C
COM
EARTH GROUND
(See note 1)
RJ31X CONN
Model 368
Cord
G
R
EEN
RE
D
BR
O
W
N
GRA
Y
HOME
TELCO
SMOKE POWER
or
ALARM PWR 2
(See note 4 &
detail A)
RELAY 2
ALARM PWR 1
BELL OUTPUT
(See note 2 & 3)
[–] [+]
RELAY 1
GND
*Cut for
dry
contact
on RLY1
JP2
37
36
35
34
33
32
31
30
TRANSFORMER
16.5 VAC 40VA
Model 1361
AUX POWER
1
2 – 12.8 VDC Reg.
470MA Incl. 16 & 17
(250 MA UL)
AUX POWER
12 – 12.8 VDC Reg.
150 MA Max.
(250 MA UL)
ALARM POWER
12 VDC Reg.
Max. 2 Amps
(1 Amp UL)
[+]
[–]
[+]
[–]
[+]
[–]
12V 5AH
BATTERY
Model 1250
RED (+)
BLACK (–)
INSTRUCTIONS
NOTE 1: Connect to cold water pipe
ground. 16 gauge at 15 feet.
NOTE 2: Terminal #27 is internally
connected to terminal #31. For dry
contact output on RELAY #1, cut jumper
JP2.
NOTE 3: Total alarm current for RELAY
1 & 2 is 2 Amps maximum (1 Amp UL)
NOTE 4:
a) RELAY # 2 can be used to RESET
SMOKE DETECTOR POWER (and fire
verification). If so, connect a jumper from
terminal 33 (+) to terminal 24. Smoke
detector power is derived from terminal
25 (+) and 26 (–). Also see detail A.
or
b) RELAY #2 can be used for a dry
contact in an alarm or trouble condition,
or for alarm power 2 by installing a
jumper from terminal 31 (+) to terminal
24. Alarm power 2 will be derived from
terminal 23 (+) and 26 (–).
To reload factory default values remove
all power from the system (AC & DC)
then short TP1 to TP2. With short still
intact, reapply power (AC then DC), wait
10 seconds, and then remove short while
still powered.
To reset control panel, short TP2 to TP3.
For further information, consult the
Instruction Manuals.
17
RED
GREEN
YELLOW
BLACK