Section 3 – System Wiring and Hookup
3–3
XL-4 and XL-5
CONNECTIONS FOR HOUSEHOLD FIRE/BURGLAR ALARM SYSTEMS UL985 AND 1023
Detail A
NOTES: For UL Installation (Household)
1- Connect to a grounded could water pipe, 16 ga. at 15
feet.
2- Total AUX. Power available is 750 mA, which
includes keypad power and expansion boards when
using a 5AH battery.
3- System must be tested on a weekly basis. For
information refer to references (N9144 & N9146,
dated 7/92).
4- Do not connect the transformer to a receptacle
controlled by a switch.
5- Installation of equipment and wiring methods are
required to be in accordance with the National
Electricians code and ANSI/NFPA no 74. More
information may be obtained from the NFPA, Battery
March Park, Quincy, MA 02269.
6- Battery capacity for Emergency Standby is a
minimum of 4 hours. Under normal conditions this
battery will last 3 years, use only exact replacements.
7- Maximum entrance time is 45 seconds, maximum
exit time is 60 seconds.
8- Maximum of four keypads.
9- Expansion Modules: Model 7015 8 zone hardwire or
7120 (XL-4) /7126 (XL-5) Multiplex module.
10- Limited energy cable must be used.
SMOKE DETECTOR
CONTROL PANEL
MODEL ESL204A
E.O.L. RELAY
TO
ZONE
UL LISTED
SMOKE
DETECTOR
MODEL
ESL445AT
LISTED
HEAT
DETECTORS
Model EOL22 2.2K EOL Resistor
BRO
W
N
RED
BL
ACK
BRO
W
N
[+] [–]
25 26
3
2
1
4
WARNING
DISCONNECT PHONE LINES PRIOR TO
SERVICING.
WARNING
THIS UNIT INCLUDES AN ALARM VERIFICATION
FEATURE THAT WILL RESULT IN A DELAY OF THE
SYSTEM ALARM SIGNAL FROM THE INDICATED
CIRCUITS. THE TOTAL DELAY (CONTROL UNIT
PLUS SMOKE DETECTOR SHALL NOT EXCEED 60
S. NO OTHER INITIATING DEVICES SHALL BE
CONNECTED TO THESE CIRCUITS UNLESS
APPROVED BY THE LOCAL AUTHORITY HAVING
JURISDICTION.
SMOKE DETECTOR
CIRCUIT
CONTROL UNIT
(ZONE)
DELAY - SEC.
MODEL DELAY - SEC*
20
*Obtain from smoke detector installation instructions.
NOTE: For installations containing multiple smoke
detectors, break the wire to maintain supervision.
CAUTION:
Incorrect connections nay result in damage to the unit.
XL-4B
CONNECTIONS FOR HOUSEHOLD FIRE/BURGLAR ALARM SYSTEMS UL985 AND 1023
NOTES: For UL Installation (Household)
1- Connect to a grounded could water pipe, 16 ga. at 15
feet.
2- Total AUX. Power available is 750 mA, which
includes keypad power and expansion boards when
using a 5AH battery.
3- System must be tested on a weekly basis. For
information refer to references (N9144 & N9146,
dated 7/92).
4- Do not connect the transformer to a receptacle
controlled by a switch.
5- Installation of equipment and wiring methods are
required to be in accordance with the National
Electricians code and ANSI/NFPA no 74. More
information may be obtained from the NFPA, Battery
March Park, Quincy, MA 02269.
6- Battery capacity for Emergency Standby is a
minimum of 4 hours. Under normal conditions this
battery will last 3 years, use only exact replacements.
7- Maximum entrance time is 45 seconds, maximum
exit time is 60 seconds.
8- Maximum of four keypads.
9- Expansion Modules: Model 7015 8 zone hardwire, or
7120 Multiplex module.
10- Limited energy cable must be used.
WARNING
DISCONNECT PHONE LINES PRIOR TO
SERVICING.
WARNING
THIS UNIT INCLUDES AN ALARM VERIFICATION
FEATURE THAT WILL RESULT IN A DELAY OF THE
SYSTEM ALARM SIGNAL FROM THE INDICATED
CIRCUITS. THE TOTAL DELAY (CONTROL UNIT
PLUS SMOKE DETECTOR SHALL NOT EXCEED 60
S. NO OTHER INITIATING DEVICES SHALL BE
CONNECTED TO THESE CIRCUITS UNLESS
APPROVED BY THE LOCAL AUTHORITY HAVING
JURISDICTION.
SMOKE DETECTOR
CIRCUIT
CONTROL UNIT
(ZONE)
DELAY - SEC.
MODEL DELAY - SEC*
20
*Obtain from smoke detector installation instructions.
NOTE: For installations containing multiple smoke
detectors, break the wire to maintain supervision.
CAUTION:
Incorrect connections nay result in damage to the unit.
SMOKE DETECTOR
CONTROL PANEL
MODEL ESL204A
E.O.L. RELAY
TO
ZONE
UL LISTED
SMOKE
DETECTOR
MODEL
ESL445AT
LISTED
HEAT
DETECTORS
Model EOL22 2.2K EOL Resistor
BRO
W
N
RED
BL
ACK
BRO
W
N
[+] [–]
25 26
3
2
1
4
Detail A
UL Listed
MODEL MBL-8
MODEL AD10-12
Bell in listed Bell
Box, Model AB
Ademco
Connect with 16
AWG wire.
(Internal conn. - 4 to
6 and 3 to 5.)
NOTES: For UL Installation (MERCANTILE)
1-
Installation of equipment and wiring methods shall be accomplished in
accordance with the National Electrical Code and ANSI/NFPA no. 70.
2-
Fire Zones shall not be employed in a Commercial application.
3-
Maximum entrance time is 15 seconds, maximum exit time is 60 seconds.
4-
For UL certified installations, this product shall be connected to a
compatible listed Digital Alarm Receiver.
5-
Installation requires circuit board enclosure tamper. Use either AMSECO
type ATS-1 or ADEMCO No. 19, closed circuit tamper switch. Mount
using the three holes provided on the side of the enclosure.
6-
The cover of the enclosure must be secured with the eleven 1/2” long No.
8-32 screws provided.
7-
Metal conduit shall be used to connect the bell to the control panel.
8-
This control unit is intended for use as a Household Fire & Burglary
Warning System Control Unit, Grade A Local Alarm Unit, Grade A Police
Station Connected Unit with basic line security, and Grade B Central
Station Burglar Alarm Unit with compatible bell, or Grade C Central
Station Burglar Alarm Unit without compatible bell.
CONNECTIONS FOR MERCHANTILE BURGLAR ALARM SYSTEM UL 365, 609, AND 1635
(NOTE: All other connections are the same as above.)
FOR ADDITIONAL INFORMATION REFER TO UL611 an UL681
20
19
18
21 22 23 24 25 26 27 28 29
TO ZONE +
COLD WATER
PIPE GROUND
1
2
3
4
5
6
2.2K
TO ZONE
TO ZONE
–
GROUND LUG
16
17
INSTALL JUMPER