XL-20 Hookup and Installation Instructions
9–22
Digits
NON-
INVERT
INVERT
TRIGGER TYPE DEFINITION
DESCRIPTION OF OPERATION
12
32
Keypad Sounder
Active when keypad sounder activates
13
33
RF Momentary
Active when keyfob momentary Trigger 1 or 2
activates
TWO-WAY VOICE - This trigger will activate when line seizure occurs if the event is
any of the following: Burglary, Fire, Duress, Keypad Panic, Keypad Fire, or Keypad
Auxiliary. It will not activate for CS Test, Openings/Closing, Trouble, Bypass, Cancel, or
Restore. It will deactivate about 1 second before disconnecting the telephone line. Also, at
the time of release, keypad sounders will be silenced for the remaining duration of the
bell output cycle. The bell will timeout or a valid User code will terminate.
NOTE: The trigger outputs are limited to approximately 50 mA each.
NONINVERT TRIGGER - The trigger output (positive to negative) is normally floating
and actively sinks (becomes a negative) on activation.
INVERT TRIGGER - The trigger output (positive to negative) is normally sinking
(negative with respect to positive), and actively floats on activation.
QUESTION 29
CS TEST TIME
DEFAULT = 0000
If the control panel transmits a system test at a specific time of day, enter the hour and
minute in military time (24-hour clock) as follows:
Question 29, L1 & L2 - Hour of Day (00 - 23)
Default = 00
Enter the hour of the day in military time: 12 A.M. - 12 P.M. (00 - 23). NOTE: Quick
Rule: 00 = Midnight; for times after 12 noon, add 12 hours to obtain the hour.
Question 29, L3 & L4 - Minute within Hour (00 - 59)
Default = 00
Example: To transmit at 5:30 PM, enter a 17 into L1 & L2 and 30 into L3 & L4.
NOTE: The CS Test Interval is selected in question 07, location 3, and is enabled in question
21, locations 3 & 4.
QUESTION 30
CID GROUP NUMBER
DEFAULT = AAAA
Question 30, L1 & L2 - Account 1 Group Number
Default = AA
Question 29, L1 & L2 - Account 2 Group Number
Default = AA
This question contains the group number that is to be sent in Contact ID format. L1 and L2
contain the group number that will be sent when using account number 1. L3 and L4
contains the group number that will be sent when using account number 2.
QUESTION 31
RF REMOTE KEYFOB 1 BUTTON DEFINITIONS
DEFAULT = 0000
Question 31, L1 - RF Remote Keyfob 1 Button 1
Default = 0
Question 31, L2 - RF Remote Keyfob 1 Button 2
Default = 0
Question 31, L3 - RF Remote Keyfob 1 Button 3
Default = 0
Question 31, L4 - RF Remote Keyfob 1 Button 4
Default = 0
In locations L1-L4, enter the digit for the desired system options from the table below.
Содержание XL-20
Страница 9: ...XL 20 Hookup and Installation Instructions 1 2...
Страница 19: ...XL 20 Hookup and Installation Instructions 4 2...
Страница 23: ...XL 20 Hookup and Installation Instructions 5 4...
Страница 33: ...XL 20 Hookup and Installation Instructions 8 4...
Страница 63: ...XL 20 Hookup and Installation Instructions 11 4...
Страница 65: ...XL 20 Hookup and Installation Instructions 12 2...
Страница 71: ...XL 20 Hookup and Installation Instructions A 6...
Страница 75: ...XL 20 Hookup and Installation Instructions B 4...
Страница 77: ...XL 20 Hookup and Installation Instructions C 2...
Страница 79: ...XL 20 Hookup and Installation Instructions D 2...
Страница 81: ...XL 20 Hookup and Installation Instructions E 2...
Страница 82: ...Notes...
Страница 83: ...1 9 Gl N9825V1 04 98 Copyright 1998 PITTWAY CORPORATION...