Auxiliary Device Current Draw Worksheet
DEVICE
CURRENT DRAW
FOR EACH
NUMBER
OF UNITS
TOTAL CURRENT
FOR EACH
XK-108 Keypad
30mA
PIR
**
Smoke Detector
**
Glassbreak Detector
**
**
**
TOTAL CURRENT FOR ALL DEVICES =
(500mA max.)
NOTE:
** If using devices such as PIRs, smoke detectors, etc., refer to
the specifications for that particular device's current draw. If
the total current draw exceeds 500mA, then use an
additional power supply.
NFPA, UL, and the California State Fire Marshal require the backup battery to provide power for
24 hours. The maximum aux. power will vary by the ampere/hour rating of the battery used:
5AH = 95mA; 7AH = 180mA; 8AH = 210mA.
13
14
DOOR CONTACT
INSIDE WALL
MOMENTARY SWITCH*
OUTSIDE MOMENTARY
SWITCH*
2.2 K EOL
RESISTOR
* SWITCHES MUST BE MOUNTED AT LEAST 54 INCHES ABOVE THE
DOOR THRESHOLD.
Содержание XL-20
Страница 9: ...XL 20 Hookup and Installation Instructions 1 2...
Страница 19: ...XL 20 Hookup and Installation Instructions 4 2...
Страница 23: ...XL 20 Hookup and Installation Instructions 5 4...
Страница 33: ...XL 20 Hookup and Installation Instructions 8 4...
Страница 63: ...XL 20 Hookup and Installation Instructions 11 4...
Страница 65: ...XL 20 Hookup and Installation Instructions 12 2...
Страница 71: ...XL 20 Hookup and Installation Instructions A 6...
Страница 75: ...XL 20 Hookup and Installation Instructions B 4...
Страница 77: ...XL 20 Hookup and Installation Instructions C 2...
Страница 79: ...XL 20 Hookup and Installation Instructions D 2...
Страница 81: ...XL 20 Hookup and Installation Instructions E 2...
Страница 82: ...Notes...
Страница 83: ...1 9 Gl N9825V1 04 98 Copyright 1998 PITTWAY CORPORATION...