6. Operation
DEPOLOX® Pool Compact
62
EN
5 To change/enable the password on Level
2, click the value for the Level 2 password.
The input menu opens.
6 Enter a combination of numbers and let-
ters with a maximum of ten characters.
7 Confirm with the “Save” button.
6.4
Web visualization
The web views integrated in the electronics
module allow you to visualize the measure-
ments and setting parameters via a standard
browser and Internet-capable devices.
Fig. 3
Example, web view DEPOLOX® Pool
Compact
The menu bar is divided into two main menus:
•
Language
•
Settings
6.4.1 Language
Selection of language.
6.4.2 Settings
NOTICE
To define or change the passwords at a later
time, Login on Level 2 is required. To disable
the passwords, define the password as “0”.
NOTICE
If alarms or errors are active, a yellow or red
message symbol is displayed in the menu
bar. Pressing the message symbol displays
the active alarms or errors.
Parameter
•
Cl2 free
•
pH
•
ORP (Redox)
•
Conductivity
•
Temperature
Setpoint:
within range
Xp:
1 to 1000
Tn:
0 to 100.0 min
Limit value Max 1:
within range
Limit value Min 1:
within range
Limit value Max 2:
within range
Limit value Min 2:
within range
System
System name:
Customizable, customer-spe-
cific device name
Date:
Date setting
Time:
00:00 to 24:00
Software version:
Display software version
Software number:
Display software number
Serial number:
Display device serial number
IP configuration
IP:
Enter a fixed IP address
(contact the network administrator)
Network mask:
Enter the subnet mask
(contact the network administrator)
Gateway:
Gateway setting
Mac:
Display the device Mac address
IP Password:
124
In order to change the IP address of the
device via the web visualization, the IP
password must first be set to “124.”
IP link 1...3:
Enter the IP address for up to three devi-
ces with the integrated web visualiza-
tion. These devices can then be called
directly from the selection menu (top
left of the web view links) via Name of
Link 1...3.