DEPOLOX® Pool Compact
4. Interfaces
31
EN
(Ch.5) Temperature - Measurement
400160
FLOAT
4
R
Measured value
400162
ASCII
10
R
Measured unit
"°C"; "°F"
400167
FLOAT
4
R
Lower range
0,0°C; 32,0°F
400169
FLOAT
4
R
Upper range
50,0°C; 122,0°F
400171
4
R
--
400173
4
R
--
Status messages
400300
UINT16
2
R
Alarm stats
0
Alarm 1
1 = Alarm pending
1
Alarm 2
1 = Alarm pending
2
Alarm 3
1 = Alarm pending
3
Alarm 4
1 = Alarm pending
4
Alarm 5
1 = Alarm pending
5
Alarm 6
1 = Alarm pending
6
Alarm 7
1 = Alarm pending
7
Alarm 8
1 = Alarm pending
400301
UINT16
2
R
Digital inputs
0
Sample water STOP - DI1
1 = DI active (open)
1
DI 2
1 = DI active (open)
2
DI 3
1 = DI active (open)
3
DI 4
1 = DI active (open)
4
DI 5
1 = DI active (open)
400302
UINT16
2
R
Relay outputs
0
Relay K1
1 = Relais aktiv
1
Relay K2
2 = Relais aktiv
2
Relay K3
3 = Relais aktiv
3
Relay K4
4 = Relais aktiv
4
Relay K5
5 = Relais aktiv
5
Relay K6
6 = Relais aktiv
400303
UINT16
2
R
---
Modbus
Register
Bit
Type
No.
Byte
Access
Designation
Description