3. Description
DEPOLOX® Pool Compact
22
EN
3.8.2 Flow cell (module name D02)
NOTICE
When connecting inductive or capacitive loads (e.g. pump with integrated switching power
supply), an additional power relay with suitable specification must be provided. Each relay
output has an integrated 3.15 A fuse as overcurrent protection.
Typical use of relays: enable contact for dosing device, control of motors or dosing pumps.
Analog outputs
4-way mA output card 0/4 to 20 mA (optional);
Freely configurable signal assignment;
Load max. 500 ohm, accuracy < 0.5 % FS ;
Galv. isolated up to 50 V relative to earth
Interfaces
RS485 interface with Wallace & Tiernan protocol for connection to
OPC server, Process Monitoring System or control system for data
visualization;
Ethernet interface (HTTP protocol/Modbus TCP protocol);
USB interface for firmware update
Housing
Dimensions (WxHxD)
9.96“ x 14.76“ x 6.42“
(253 x 375 x 163 mm)
Weight
approx. 5.5 lbs (2.5
k)g
Connections
Pressurized version
Inlet and outlet: G 1/2” A thread connec-
tion
Flow control valve
Sample water flow
0.15 gpm (33 l/h), controlled, preset at
the factory
Flow control range
4 to 45 psig (0.25 to 3.0 bar)
Back pressure
Pressurized version: max. 22 psig (1.5 bar)
Multi-sensor
Switching point
5.5 gal/hr ±0.8 gal/hr (21 l/h ±3 l/h)
Switching hysteresis
0.53 gal/hr (2 l/h)
Temperature sensor
Pt1000
Operating concitions
Water quality
Brine and pool water acc. to standard
Storage temperature
-4 to 158 °F (-20 to +70°C)