DEPOLOX® Pool Compact
5. Installation
47
EN
1 Switch on power supply.
2 Perform initial configuration:
•
Set “MANUAL” mode
•
Select the language
•
Set the date and time
•
Enter the system name
3
Chlorine measurement
•
Set the dosing output for Cl
2
, if neces-
sary set positioner running time “Ty,”
“Tp” or “Max. pulses/min.”
•
Check setpoint for Cl
2
control, change
if necessary (only for Cl
2
closed-loop
control).
•
Adapt values for “Xp” and “Tn” to con-
trol loop.
•
Check the limit values 1 and 2 for Cl2
(“Min" and “Max"), adjust if neces-
sary.
•
Check the measurement range for Cl2,
adjust if necessary.
4
pH measurement
•
Set the dosing output for pH, if neces-
sary set positioner running time “Ty,”
“Xsh,” “Tp” or “Max. pulses/min.”
•
Set the control direction (for pumps
2P).
•
Check the setpoint for pH control,
adjust if necessary.
•
Adapt the values for "Xp" and "Tn" to
the control loop, if necessary optimize
in small steps.
•
Check the limit values 1 and 2 for pH
(“Min" and “Max"), adjust if neces-
sary.
5 ORP (Redox) measurement (if available)
•
Check the limit values 1 and 2 for ORP
(“Min" and “Max"), adjust if neces-
sary.
•
Check the measurement range for
ORP, adjust if necessary.
6 Conductivity measurement (if available)
•
Check the limit values 1 and 2 for con-
ductivity (“Min" and “Max"), adjust if
necessary.
•
Check the measurement range for
conductivity, adjust if necessary.
•
Activate controller for conductivity, if
necessary.
•
Set control outputs for conductivity, if
necessary.
•
Set the setpoint for conductivity, if
necessary.
7 Adapt the values for "Xp" and "Tn" to the
control loop, if necessary.
8 Configure alarms as required.
9 Configure analog outputs as required.
10 Define function DI2 and DI3.
11 Parametrize interfaces.
12 In Manual mode, check all connected
dosing devices for correct functioning.
13 Test Cl
2
feed lockout activated functions
such as circulation monitoring and Sample
water Stop.
14 Carry out initial calibration of the sensors
after a running time of approx. one hour.
15 Switch to Automatic mode and monitor
system for correct functioning.
16 Repeat calibration after a running-in time
of approx. 24 hours.
NOTICE
These values may be optimized later by Auto
tune or manually.