DEPOLOX® Pool Compact
3. Description
13
EN
3.5.5 Alarms
The electronics module supports up to eight
freely configurable alarms. The alarms can be
assigned to a relay contact and noted on the
color display. At the same time, a message is
displayed in the message window and the
message system is displayed. The number of
available relays depends on the configuration.
A maximum of six alarm relays are possible,
depending on if the controller disinfection
output is used. The alarm relays can be used,
for example, for safety deactivation of dosing
when specific values are exceeded or not rea-
ched. Each alarm can be assigned the follo-
wing functions. Multiple assignment is
possible:
Acknowledgment “none“
•
The alarm symbol and the message sym-
bol light up in the event of an alarm and
go out automatically when the condition
is eliminated.
•
Unlatched alarms are displayed in yellow
as messages.
•
The relay is active when the alarm symbol
is displayed and the alarm is active.
Fig. 2
Acknowledgment “none“
Acknowledgment “ACK with reset“
•
In the event of an alarm, the alarm sym-
bol and the message symbol flash and the
relay is active until acknowledged.
•
The alarm symbol and the message go out
even if the conditions still apply when the
alarm is acknowledged.
•
Latched alarms are displayed in red as
messages.
•
The relay becomes inactive after acknow-
ledgment if the condition is still pending.
Fig. 3
Acknowledgment “ACK with reset“
Acknowledgment “simple ACK“
•
The relay becomes active as soon as the
alarm is active.
•
In the event of an alarm, the alarm sym-
bol and the message symbol flash until
the alarm is acknowledged.
•
If the condition is no longer present when
the alarm is acknowledged, the alarm
symbol goes out and the message disap-
pears.
•
If the condition is still present when the
alarm is acknowledged, the alarm symbol
and the message are reset from flashing
to a permanent state. The alarm symbol
and the message light up until the condi-
tion is eliminated (auto-reset).
•
Latched alarms are displayed in red as
messages.
•
The relay is only deactivated when the
condition has been eliminated and ack-
nowledged.
Fig. 4
Acknowledgment “simple ACK“
Limit value
Min 1 and Min 2
=>
all measuring
values can be selec-
ted individually
Limit value
Max 1 und Max 2
Digital inputs
=>
1 to 5 can be selec-
ted individually
Error
Alarm condition
Symbol without
Relay without
Symbol with
Relais with
delay time
delay time
delay time
delay time
Alarm condition
Symbol without
Relay without
Symbol with
Relay with
delay time
delay time
delay time
delay time
flashing
flashing
Alarm condition
Symbol without
Relay without
Symbol with
Relay with
delay time
delay time
delay time
delay time
flashing
flashing