All the functions listed above can be selected using the function keys or the push encoder, as described in the general
introduction.
–
During setting, the value to change will flash.
The hours/minutes or minutes/seconds on the timer are modified separately.
If confirmation is not given within 5 seconds, it will automatically validate the displayed value.
–
The controller begins regulation when the value of the energy regulator is anything other than “0”, based on
the regulation value set by the relative parameters:
–
Regulator 1: 3” ON (r19)/45” OFF (r20)
–
Regulator 2: 4” ON (r21)/38” OFF (r22)
–
Regulator 3: 5” ON (r23)/32” OFF (r24)
–
Regulator 4: 7” ON (r25)/29” OFF (r26)
–
Regulator 5: 9” ON (r27)/30” OFF (r28)
–
Regulator 6: 13” ON (r29)/32” OFF (r30)
–
Regulator 7: 21” ON (r31)/37” OFF (r32)
–
Regulator 8: 45” ON (r33)/60” OFF (r34)
–
Regulator 9: always ON (r35/r36)
–
Heating is interrupted when the power regulator is set with a value of “0” or when the controller is switched OFF.
–
When countdown ends (time at 00:00), the buzzer will sound until the button on the push encoder (or one of the 6
function keys) is pressed or or until the timeout interval set by the relative parameter (e2) elapses, with a cycle of 0.5
“ON/0.5” OFF. This does not affect the regulation, the device will continue normal regulation.
Management of technical room fan output and ON-OFF output
–
If one of the available outputs is configured as “technical room fans” (value set to 11), the fans are always on
(except for models with J/K thermocouples, where they are activated when the threshold set by parameter r37
is exceeded).
–
–
If one of the available outputs is configured as “ON-OFF” (value set to 14), the relay will operate as follows:
–
OFF when the device is on stand-by mode
–
ON under all other conditions