Operation
–
All the functions listed above can be selected using the function keys or the push encoder, as described in the general
introduction.
–
During setting, the value to change will flash.
The hours/minutes or minutes/seconds on the timer are modified separately.
If confirmation is not given within 5 seconds, it will automatically validate the displayed value.
–
Except for ∆T mode, the controller heats when the value of the regulation probe is lower than the set value. It
interrupts heating when the value exceeds it. Heating is restored when the value goes below the set value again.
Regulation continues until the regulator is switched OFF.
–
Heating in ∆T mode:
cooking continues until the temperature detected by the needle probe reaches the core setpoint. Once it has
reached this setpoint, the heating relay is deactivated.
The working setpoint is relative to the temperature detected by the needle probe, that is “
temperature detected by the
needle probe + Delta T
setpoint”
–
When the set temperature is reached, a warning icon
will appear on the screen.
The icon will disappear only when the temperature setpoint is changed or the controller switched
off.
–
Heating is interrupted when the controller is switched off.
–
When the needle temperature is reached or the countdown ends (time at 00:00), the buzzer will sound until the button on the
push encoder (or one of the 6 function keys) is pressed or until the timeout interval set by the relative parameter (e2) elapses,
with a cycle of 0.5 “ON/0.5” OFF. This does not affect the regulation, the device will continue normal regulation.
Management of technical room fan output and ON-OFF output
–
If one of the available outputs is configured as “technical room fans” (value set to 11), the fans are always on
(except for models with J/K thermocouples, where they are activated when the threshold set by parameter r37
is exceeded).
–
–
If one of the available outputs is configured as “ON-OFF” (value set to 14), the relay will operate as follows:
–
OFF when the device is on stand-by mode;
–
ON under all other conditions.