Operation
–
All the functions listed above can be selected using the function keys or the push encoder, as described in the general
introduction.
–
During setting, the value to change will flash.
The hours/minutes or minutes/seconds on the timer are modified separately.
If confirmation is not given within 5 seconds, it will automatically validate the displayed value.
–
The controller begins regulation when the value of the energy regulator is anything other than “0”, based on the
regulation value set by the relative parameters:
–
Regulator 1: 2” (r19) ON/10” (r20) OFF
–
Regulator 2: 4” (r21) ON/10” (r22) OFF
–
Regulator 3: 6” (r23) ON/10” (r24) OFF
–
Regulator 4: 8” (r25) ON/10” (r26) OFF
–
Regulator 5: 10” (r27) ON/10” (r28) OFF
–
Regulator 6: 12” (r29) ON/10” (r30) OFF
–
Heating is interrupted when the power regulator is set with a value of “0” or when the controller is switched OFF.
–
At the end of the countdown (when the time is 00:00), the buzzer will sound until the button on the push encoder (or
one of the six function keys) is pressed or until the timeout interval set by the relative parameter (e2) elapses, with a
cycle of 0.5 ”ON/0.5” OFF. This does not affect the regulation, the device will continue normal regulation.
Management of technical room fan output and ON-OFF output
–
If one of the available outputs is configured as “technical room fans” (value set to 11), the fans are always on
(except for models with J/K thermocouples, where they are activated when the threshold set by parameter r37
is exceeded).
–
–
If one of the available outputs is configured as “ON-OFF” (value set to 14), the relay will operate as follows:
–
OFF when the device is on stand-by mode
–
ON under all other conditions