Basic functions
Basic functions
Basic functions
Basic functions
The following basic functions are available for all the configurations.
Technical room fans (only for models with J/K thermocouples)
When the temperature recorded by the on-board probe exceeds the threshold set by parameter “
r37
”, the relay
configured as “
Fans
” is activated.
The hysteresis to deactivate the relay is set at 2°C.
If one of the relays is set as “
Fans
” but there is no on-board probe or there is a probe error, the relay will always
be active.
When the heating output is active (either in power-controlled and in temperature-controlled models), the icon
will be
displayed in the top-left corner.
Heating
When regulation is managed with a temperature setpoint, the relay output for the heaters can be
managed by conventional or PI-type regulation.
Activating the buzzer when the setpoint is reached
For applications with temperature regulation, the first time the setpoint regulation temperature is reached (including the
MELT function), the buzzer will sound according to the configuration set by parameter “
e2
”.
The buzzer will work with the same logic as the “green light” which indicates the setpoint has been reached.