Manufacturer Specific Profile Area
CAN-CBX-AI420
Manual • Doc.-No.: C.3030.21 / Rev. 1.4
Page 91 of 103
7.11.3 Chopping Mode (2311
h
)
Index
Sub-
index
Description
Value range
Default
Data type
Access
mode
2311
h
0
Number of entries
4
4
unsigned 8
ro
1
Chop_Mode_1
0, 1
1
boolean
rw
2
Chop_Mode_2
0, 1
1
boolean
rw
3
Chop_Mode_3
0, 1
1
boolean
rw
4
Chop_Mode_4
0, 1
1
boolean
rw
If the chopping mode is activated for the A/D-converter, the offset of the measured value is reduced.
But the chopping mode reduces also the conversion rate of the A/D-converter.
Details about the chopping mode can be taken from the data sheet
[9]
of the A/D-converter AD7732
(e.g. under
www.analog.com
).
It is recommended to operate with enabled chopping mode (Chop_Mode_x: "1" ).
Wertebereich:
Chop_Mode_x
Value
Meaning
false
0
Chopping mode disabled
true
1
Chopping mode enabled